Primary switched mode power supply, three-phase
PSR 500/24-5 - Discontinued items – not for new applications
| Product | Primary switched mode power supply, three-phase |
| Order number | PSR 500/24-5 |
| Series | PSR |
Input
| Rated input voltage | 400 Vac to 500 Vac |
| Input voltage range | 325 Vac to 550 Vac |
| Input voltage range | 460 Vdc to 550 Vdc |
| Rated input current (rated load) (400Vac) | 0.30 A |
| Rated frequency range AC | 50 Hz to 60 Hz |
| Rated frequency range DC | 0 Hz |
| Inrush current limitation NTC < | 20 A |
| Recommended preliminary fuse | 10A, 16A, B/C-Char. |
| Mains failure bridging (rated load) (400Vac) | 10.0 ms |
Output
| Power | 120 W |
| Rated output voltage | 24 Vdc |
| Rated Output Current | 5 A |
| Output voltage range | 22.8 Vdc to 28.8 Vdc |
| Output Current Limitation (Constant Current) typ. | 6 A |
| Ripple (rated load) typ. | 100 mVss |
| Max. power loss | 17.9 W |
| Max. feedback resistance | 30 Vdc |
| Verlustleistung Leerlauf (400Vac) | 2.30 W |
| Verlustleistung Nennlast (400Vac) | 15.30 W |
| Überspannungsschutz des Ausgangs | 33.0 Vdc |
| Parallel connection possible | Yes |
| Series connection possible | Yes |
Signaling
| Status display | Green, red LED |
Environment
| Ambient temperature | -10 °C to 60 °C / 14 °F to 140 °F |
| Storage temperature | -25 °C to 85 °C / -13 °F to 185 °F |
| Humidity without condensation | 30 % to 85 % |
| Cooling type | natural convection |
| Required minimum distance (side) | 15 mm |
| Required minimum distance (top/bottom) | 70 mm |
Protection and Safety
| Degree of pollution | 2 |
| Protection class according to EN 61140 | I |
Size and Weight
| Width | 65 mm / 2.56 in |
| Height | 120 mm / 4.72 in |
| Depth | 122 mm / 4.8 in |
| Weight | 0.75 kg / 1.653 lbs |
| cURus | UL 60950-1 - Recognized |
| cULus | UL 508 - Listed |