EB-1724-2020-0F
2-Channel circuit breaker, EasyB
Version EB-1724-2020-0F
Input rated voltage
24 Vdc
Output rated current
2 x 1 A, NEC Class 2
Version | Input rated voltage | Output rated current | ||
---|---|---|---|---|
EB-1724-2020-0F | 24 Vdc | 2 x 1 A, NEC Class 2 | ||
EB-1724-2040-0F | 24 Vdc | 2 x 2 A, NEC Class 2 | ||
EB-1724-2060-0F | 24 Vdc | 2 x 3 A, NEC Class 2 | ||
EB-1724-2080-0F | 24 Vdc | 2 x 4 A, NEC Class 2 | ||
EB-1724-2120-0F | 24 Vdc | 2 x 6 A | ||
EB-1724-2160-0F | 24 Vdc | 2 x 8 A | ||
EB-3724-2160-0F | 24 Vdc | 0.5 - 8 A, adjustable (0,5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A) |
DOWNLOADS
Technical files
Instruction manual
Approvals / Manufacturer's declaration
EU-Declaration of Conformity
Technical data for EB-1724-2020-0F
Input | |
---|---|
Input rated voltage | 24 Vdc |
Input voltage range | 18 - 30 Vdc |
Maximal residual ripple of supplied input voltage | 3 % |
Max. total input current | 2 x 1 A |
Max. input current for each pole of terminal | 10 A (-), 40 A (+) |
Required input voltage for turning-on of outputs | 17.5 V (Turn-off Threshold 16.7 V), ± 0.7 V |
Max. power losses | 0,5 W |
Over voltage protection | Suppressor diode 33 V |
Stand-by current | 40 mA @ 24 V |
Power losses in stand-by mode | 0,4 W |
Turn on capacity | 20 mF @ 24 Vdc / 2,5 mm² / 2,5 m |
Output | |
---|---|
Output rated voltage | 24 Vdc |
Output rated current | 2 x 1 A, NEC Class 2 |
Maximum voltage drop between input and output | 24 mV |
Initialization time of module | 52 ms |
Turn-on delay of outputs | min. 50 ms / max. 5 s |
Waiting periode after switch-off of an output | 500 ms (Short circuit) … 5 s (Overload) |
Maximum turn-on capacity for each channel | 20 mF |
Parallel use of outputs | Not allowed |
Serial use of outputs | not allowed |
Resistance to reverse feed max. | 35 Vdc |
Efficiency | 99.0 % |
Signaling | |
---|---|
Bus communication | Read:-state (tripped, On, Off) -set/active current -input voltage -firmware version/serial number Write:-state (on, off, reset) |
Status indicator | LED (red, green, orange) |
Signal output | Output status, short circuit proof high = Channel on, low = Channel off, fault |
Signal output (ON/OFF/Reset) | - |
Approvals | |
---|---|
Approvals | cURus, cULus |
Environment | |
---|---|
Type of cooling | Natural convection |
Ambient temperature | -25 °C … +70 °C |
Storage temperature | -25 °C … +85 °C |
Relative humidity | 5 … 96 %, without condensation |
Required minimum spacing (left/right) | 0 mm |
Required minimum spacing (over/under) | 30 mm |
Safety and protection | |
---|---|
Protection index | IP 20 |
Safety class | III, without PE connection |
Degree of pollution | 2 |
Terminal and mounting | |
---|---|
Terminals input, (spring clamp terminal) | max. 16 mm² |
Terminals output, (spring clamp terminal) | max 2,5 mm² (2 x "+") |
Terminals signalling, (spring clamp terminal) | max. 2,5 mm² |
Mounting position | horizontal for standard rail DIN TS35 |
Measures and weights | |
---|---|
Weight | 0.048 kg |
Width | 12 mm |
Height | 99.3 mm |
Depth | 60 mm |
Info on EasyB 2-Channel thermomagnetic, adjusted internal fuse, communicative series
General Data
- Ambient temperature -25 °C … +70 °C
- With thermomagnetic characteristic
- Up to 40 fuse channels stackable side by side
- Multi-coloured LED and status display button
- Efficiency up to 99 %
- Protection index IP 20
Benefits
- Compact design - 2 independent channels in 12 mm width
- Automatic channel assignment
- Additional load outputs through output expanders mountable side by side
- Internal fuse adapted to the tripping current