Uninterruptible power supply
PCC-1024-050-2U
Characteristics
Benefits
› Combined power supply with charge and control unit
› Fast tripping of conventional circuit breakers
› Battery modules get detected automatically
› Reliable signalling when there is low remaining life expectancy of connected battery modules
› Extended life expectancy through temperature controlled battery management
› Reliable supply of industrial PC's
› 3 years warranty
| Product | Uninterruptible power supply |
| Order number | PCC-1024-050-2U |
| Series | COMBI UPS |
Input
| Rated input voltage | 100 Vac to 240 Vac |
| Input voltage range | 90 Vac to 264 Vac |
| Input voltage range | 90 Vdc to 264 Vdc |
| Rated input current (rated load) (100Vac) | 2.00 A |
| Rated input current (rated load) (230Vac) | 0.95 A |
| Inrush current limitation NTC < | 30 A |
Output
| Power | 120 W |
| Rated output voltage | 24 Vdc |
| Rated Output Current | 5 A |
| Output Current Limitation (Constant Current) typ. | 6.5 A |
| Ripple (rated load) typ. | 50 mVss |
| Max. feedback resistance | 35 Vdc |
| Überspannungsschutz des Ausgangs | 38.0 Vdc |
| Parallel connection possible | Nur mit Redundanzmodul, max. 5 A Ausgangsstrom |
Signaling
| Status display | Green, yellow, red LED |
| Communication | USB 2.0 |
Environment
| Ambient temperature | -25 °C to 70 °C / -13 °F to 158 °F |
| Storage temperature | -25 °C to 85 °C / -13 °F to 185 °F |
| Humidity without condensation | 5 % to 96 % |
| Cooling type | natürliche Konvektion |
| Required minimum distance (side) | 0 mm |
| Required minimum distance (top/bottom) | 50 mm |
Size and Weight
| Width | 55 mm / 2.17 in |
| Height | 127 mm / 5 in |
| Depth | 118 mm / 4.65 in |
| Weight | 0.75 kg / 1.653 lbs |
| cULus | UL 61010 - Listed |