Redundancy module
PC-0624-400-0
Characteristics
Benefits
› High efficiency
› Error message via relay contact and LEDs
› Safe parallel operation to increase power
› Fully compatible with Top and Power Boost for your power supplies
› Active operation for minimal power loss even in the event of a short-circuit on the secondary side
› Based on Mosfet technology
› 3 years warranty
| Product | Redundancy module |
| Order number | PC-0624-400-0 |
| Series | PC RE |
Input
| Rated input voltage | 24 Vdc |
| Input voltage range | 10 Vdc to 36 Vdc |
| Rated input current | 40 A |
Output
| Rated output voltage | 24 Vdc |
| Rated Output Current | 40 A |
| Output voltage range | 10 Vdc to 36 Vdc |
| Power boost | 200 A, 50 ms / 120 A, 4 s / 100 A, 8 s |
| Max. voltage drop between input and output | 100 mV |
| Max. power loss | 9.5 W |
| Max. feedback resistance | 37 Vdc |
| Parallel connection possible | Ja |
Signaling
| Signal output | Relay contact |
| Status display | 2 x Green LED |
Environment
| Climate class according to EN 60721 | 3K3 |
| Ambient temperature | -40 °C to 70 °C / -40 °F to 158 °F |
| Storage temperature | -40 °C to 85 °C / -40 °F to 185 °F |
| Humidity without condensation | 5 % to 96 % |
| Cooling type | natural convection |
| Required minimum distance (side) | 0 mm |
| Required minimum distance (top/bottom) | 30 mm |
Protection and Safety
| Degree of pollution | 2 |
| Protection class according to EN 61140 | III, without PE connection |
| Safety extra low voltage (SELV/PELV) | EN 60950 (SELV), EN 60204 (PELV) |
Size and Weight
| Width | 42 mm / 1.65 in |
| Height | 127 mm / 5 in |
| Depth | 112.5 mm / 4.43 in |
| Weight | 0.42 kg / 0.926 lbs |
| EMV-Richtlinie | EN 61204-3 |
| Low Voltage Directive | EN 60950-1 + A11 + A1 + A12 + AC + A2 |
| Zulassung Schiff |
DNV-CG-0339 |
| cULus | UL 508 - Listed |
| cURus | UL 60950-1 - Recognized |