Primary switched-mode power supply, single-phase
PMC-0124-013-0
Characteristics
Benefits
› Strong and compact
› Narrowest construction width and maximum flexibility
› Optimal protection against shock and vibration loads
› 3-year warranty
| Product | Primary switched-mode power supply, single-phase |
| Order number | PMC-0124-013-0 |
| Series | POWER ADVANCED |
Input
| Rated input voltage | 100 Vac to 240 Vac |
| Input voltage range | 81 Vac to 264 Vac |
| Input voltage range | 120 Vdc to 300 Vdc |
| Rated input current (rated load) (100Vac) | 0.49 A |
| Rated input current (rated load) (230Vac) | 0.28 A |
| Switch-on time (100Vac) | 2.30 s |
| Switch-on time (230Vac) | 0.74 s |
| Rated frequency range AC | 47 Hz to 63 Hz |
| Rated frequency range DC | 0 Hz |
| Inrush current limitation NTC < | 30 A |
| Recommended preliminary fuse | 6A, 10A, 16A, B/C-Char. |
| Mains failure bridging (rated load) (100Vac) | 20.0 ms |
| Mains failure bridging (rated load) (230Vac) | 120.0 ms |
Output
| Power | 31 W |
| Rated output voltage | 24 Vdc |
| Rated Output Current | 1.3 A |
| Output voltage range | 24 Vdc to 28 Vdc |
| Max. feedback resistance | 35 Vdc |
| Verlustleistung Leerlauf (230Vac) | 0.50 W |
| Verlustleistung Nennlast (230Vac) | 0.50 W |
| Parallel connection possible | with redundancy module |
| Series connection possible | Yes |
Environment
| Ambient temperature | -25 °C to 70 °C / -13 °F to 158 °F |
| Humidity without condensation | 5 % to 96 % |
| Required minimum distance (side) | 0 mm |
| Required minimum distance (top/bottom) | 30 mm |
Protection and Safety
| Protection class according to EN 61140 | II |
Size and Weight
| Width | 22.5 mm / 0.89 in |
| Depth | 94 mm / 3.7 in |
| Weight | 0.13 kg / 0.287 lbs |