Primary switched mode power supply, three-phase
PCC-0324-200-2
Characteristics
Benefits
› Strong and compact
› Narrowest construction width and maximum flexibility
› Surge-proof up to 4kV
› Optimally protected against shock and vibration loads
› Permanent 110% overload capacity (<45°C)
› 150% power boost for 5s
› 3-year warranty
| Product | Primary switched mode power supply, three-phase |
| Order number | PCC-0324-200-2 |
| Series | POWER ADVANCED |
Input
| Rated input voltage | 400 Vac to 500 Vac |
| Input voltage range | 320 Vac to 575 Vac |
| Input voltage range | 450 Vdc to 800 Vdc |
| Rated input current (rated load) (500Vac) | 0.62 A |
| Rated frequency range AC | 47 Hz to 63 Hz |
| Inrush current limitation NTC < | 30 A |
| Recommended preliminary fuse | 6A, 10A, 16A, B/C-Char. |
Output
| Power | 480 W |
| Rated output voltage | 24 Vdc |
| Rated Output Current | 20 A |
| Output voltage range | 23 Vdc to 28.5 Vdc |
| Output Current Limitation (Constant Current) typ. | 23 A |
| Power boost | 30A / 5s |
| Max. feedback resistance | 35 Vdc |
| Überspannungsschutz des Ausgangs | 40.0 Vdc |
| Parallel connection possible | mit Redundanzmodul |
| Series connection possible | Ja |
Signaling
| Status display | Green LED |
Environment
| Ambient temperature | -25 °C to 70 °C / -13 °F to 158 °F |
| Storage temperature | -40 °C to 85 °C / -40 °F to 185 °F |
| Humidity without condensation | 5 % to 96 % |
| Cooling type | natürliche Konvektion |
| Required minimum distance (side) | 0 mm |
| Required minimum distance (top/bottom) | 45 mm |
Protection and Safety
| Degree of pollution | 2 |
| Protection class according to EN 61140 | I |
Size and Weight
| Width | 55 mm / 2.17 in |
| Height | 127 mm / 5 in |
| Depth | 125 mm / 4.92 in |
| Weight | 1.15 kg / 2.535 lbs |
| cULus | UL 61010 - Listed |