Safety isolating transformer
EL 50/12
Characteristics
General data
The safety transformers of the EL series provide safe galvanic isolation of the primary circuit from the secondary circuit and are manufactured according to EN (IEC) 61558-2-6. By limiting the output voltage, the transformers are suitable for the construction of SELV and PELV circuits.
Benefits
› Solder connection for free wiring
› With dual output coils for series and parallel connection
› Excellent corrosion protection and low noise emission thanks to BLOCK IMPEX vacuum impregnation
› Easy mounting with a sturdy metal base plate featuring elongated holes
| Product | Safety isolating transformer |
| Order number | EL 50/12 |
| Series | EL |
| Power | 50 VA |
| Input | 230 V |
| Output | 2 x 12 V • 2.08 Aac |
| Phases | 1 |
| Frequency range | 50 Hz to 60 Hz |
| No-Load Losses | 3.5 W |
| EN Insulation class | E (120°C) |
| Duty Cycle | 100 % |
| Wire material | Copper |
| Efficiency | 81 % |
General
| Short circuit proof | not short-circuit proof |
| Switching group | Iii0 |
| Cooling type | AN |
Environment
| Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
| Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
| Protection type | IP00 |
| Protection class (prepared) | II |
| Overvoltage category | III |
| Degree of contamination | 2 |
Electrical Connections
| Input terminal | Soldering eye |
| Output terminal | Soldering eye |
Size and Weight
| Width | 59 mm / 2.32 in |
| Height | 67 mm / 2.64 in |
| Depth | 75 mm / 2.95 in |
| Weight | 0.979 kg / 2.158 lbs |
| Low Voltage Directive | EN 61558-2-6 |