2-pole physical isolation
EB-PT2-0 - Discontinued items – not for new applications
Characteristics
Benefits
› Two-pole physical isolation with galvanic isolation, to be added to the right side of circuit breaker channels with single alarm signal.
› Use for tripping currents up to 6 A
› All functions of the circuit breaker (communication, characteristics) can be used continuously.
› Automatic feedthrough of all signal levels
| Product | 2-pole physical isolation |
| Order number | EB-PT2-0 |
| Series | EB-ACCESSORIE |
Input
| Rated input voltage | 24 Vdc |
| Max. continuous current of the module | 6 A |
| Max. continuous current feed terminal (+) | 40 A |
| Max. ripple of the feeding input voltage | 3 % |
Output
| Rated output voltage | 24 Vdc |
| Max. voltage drop between input and output | 273 mV |
| Max. power loss | 2 W |
| Max. feedback resistance | 35 Vdc |
| Parallel connection of outputs | Nicht erlaubt |
| Series connection of outputs | Nicht erlaubt |
Signaling
| Signal input | Steuereingang, DC 24 V (18 - 30 V), Hysterese > 14,2 V ein, < 10,0 V aus, Stromaufnahme 150µA @ 24 V, high = geschlossen, low = getrennt |
Environment
| Climate class according to EN 60721 | 3K3 |
| Ambient temperature | -25 °C to 70 °C / -13 °F to 158 °F |
| Storage temperature | -25 °C to 85 °C / -13 °F to 185 °F |
| Humidity without condensation | 5 % to 96 % |
| Cooling type | natural convection |
| Required minimum distance (side) | 0 mm |
| Required minimum distance (top/bottom) | 30 mm |
Protection and Safety
| Degree of pollution | 2 |
| Degree of protection according to EN 60529 | IP 20 |
Size and Weight
| Width | 12 mm / 0.47 in |
| Height | 99 mm / 3.9 in |
| Depth | 60 mm / 2.36 in |
| Weight | 0.07 kg / 0.154 lbs |