HF1K 50-400

Harmonic filter HF1K 400

Version HF1K 50-400
Rated voltage 3 x 400 Vac Rated current 3 x 73 A Rated load power 60.35 HP
Version Rated voltage Rated current Rated load power
HF1K 7-400 3 x 400 Vac 3 x 10 A 7.38 HP
HF1K 13-400 3 x 400 Vac 3 x 19 A 14.75 HP
HF1K 18-400 3 x 400 Vac 3 x 26 A 20.12 HP
HF1K 24-400 3 x 400 Vac 3 x 35 A 26.82 HP
HF1K 30-400 3 x 400 Vac 3 x 43 A 34.87 HP
HF1K 50-400 3 x 400 Vac 3 x 73 A 60.35 HP
HF1K 70-400 3 x 400 Vac 3 x 101 A 84.48 HP
HF1K 100-400 3 x 400 Vac 3 x 144 A 120.69 HP
Image of BLOCK Item: HF1K 50-400

Technical Data for HF1K 50-400

Operating data
Rated voltage 3 x 400 Vac
Voltage range 360-440 Vac
Rated current 3 x 73 A
THD-I 8 % (nominal load)
Rated load power 60.35 HP
Description of the load Symmetrical loading by converters with B6U input rectifiers
Overrating Capacity 150 % for 60 sec. every 10 min.
Efficiency 99 %
Power loss 412 W
Capacitive idle power 10 kVAr
Input
Rated frequency 50 - 60 Hz
Approvals
Approvals cURus
Environment
Ambient temperature 14 °F to 113 °F,
without condensation
Type of cooling Air natural
MTBF @ 122 °F/500 V (Mil-HB-217F) >500.000 h
@ 40°C/400Vac
Safety and protection
Type Open type
Insulation class H
Protection index IP 00
Safety class I
Terminal and mounting
Terminals phase Copper tab, M10 bolt
Connection type Bolt, M6
Fixing method Mounting lugs
Measures and weights
Depth 12.60 inch
Height 12.40 inch
Width 21.46 inch
Weight 166.45 lbs
Notes
* IE2 efficiencies of the motors and an efficiency
>96 % assumed

Information for HF1K 400 series

General Data
  • Degree of protection IP 00
  • Load rated capacity 5.5 - 90 kW
  • Ambient temperature 14 °F / -10 °C to 113 °F / +45 °C
  • Insulation class H
  • Rated voltage 3 x 400 Vac
  • THD-I <8 % in rated operation
  • Rated current 3 x 10 - 3 x 144 A
Benefits
  • Harmonic filter with minimum capacitive idle reactive power
  • Use of the HF1K as a central hum filter for multiple converters possible
  • Sinusoidal current consumption from the main in devices with uncontrolled B6U diode rectifiers
  • Compliance with EN 61000-3-2, EN 61000-3-12
  • Support in the compliance with IEEE 519, D-A-CH-CZ
  • Power factor >0,95 at rated current
  • Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor
  • Operation at 50 - 60 Hz possible
  • Very good corrosion protection and low noise due to vacuum impregnation

Our recommendations for you

BLOCK product: LR3-AD080-404-0
LR3-AD080-404-0
Line reactor, three-phase
3 x 400 Vac, 3 x 4 - 3 x 900 A, 7,350 – 0,024 mH, Use as line reactor, commutating reactor or PFC reactor
View accessory
BLOCK product: HLD 110-500/75
HLD 110-500/75
Radio interference suppression filter, three-phase
3 x 520 Vac, 3 x 8 – 3 x 250 A, Leakage current 20.00 to 37.00 mA, For enhanced EMI suppression
View accessory
BLOCK product: LR3 40-4/80
LR3 40-4/80
Line reactor, three-phase
3 x 400 Vac, 3 x 2 – 3 x 1600 A, 0.019 – 18.500 mH, Use as line reactor, commutating reactor or PFC reactor
View accessory