Harmonic filter, three-phase
HF1K 50-400
Characteristics
Benefits
› Sinusoidal current consumption from the main in devices with uncontrolled B6U diode rectifiers
› Compliance with EN 61000-3-2, EN 61000-3-12
› Support in the compliance with IEEE 519, D-A-CH-CZ
› Cos(phi) 0,95 at rated current
› Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor
› Harmonic filter with minimum capacitive idle reactive power
› Very good corrosion protection and low noise thanks to vacuum impregnation
› Operation at 50 - 60 Hz possible
› Use of the HF1K as a central hum filter for multiple converters possible
| Product | Harmonic filter, three-phase | 
| Order number | HF1K 50-400 | 
| Series | HF1K | 
| Inductance | 3x 4.2 mH | 
| Rated current | 3x 73 Aac | 
| Linear current | 3x 109.5 Aac | 
| Rated voltage range | 360 V to 440 V | 
| Rated voltage | 400 V | 
| Phases | 3 | 
| Frequency range | 50 Hz to 60 Hz | 
| Motor or converter power | 45 kW / 60.35 HP | 
| EN Insulation class | H (180°C) | 
| UL Insulation class | class 180 | 
| Duty Cycle | 100 % | 
| Power loss | 412.00 W | 
| Wire material | Copper | 
General
| Duty Cycle | 100 % | 
| Cooling type | AN | 
| Switching group | III0 | 
Environment
| Ambient temperature | -10 °C to 45 °C / 14 °F to 113 °F | 
| Max. installation height | 1,000 m / 3,281 ft | 
Protection and Safety
| Protection type | IP00 | 
| Protection class (prepared) | I | 
| Degree of contamination | 2 | 
Electrical Connections
| Input terminal | Flat copper connection | 
| Output terminal | Flat copper connection | 
| Terminal PE | Bolt connection | 
Size and Weight
| Width | 545 mm / 21.46 in | 
| Height | 315 mm / 12.4 in | 
| Depth | 222 mm / 8.74 in | 
| Weight | 83 kg / 182.983 lbs | 
| Low Voltage Directive | EN 61558-2-20 | 
| RoHS compliant | EN IEC 63000 | 
| Approval cURus - Recognized | UL 508; CSA 22.2 | 
 
            
    
                 
         
        