EB-2724-040-4

1-Channel circuit breaker thermomagnetic, EasyB

Version EB-2724-040-4
Input rated voltage 24 Vdc Output rated current 4 A
Version Input rated voltage Output rated current
EB-2724-010-0 24 Vdc 1 A
EB-2724-010-4 24 Vdc 1 A
EB-2724-020-0 24 Vdc 2 A
EB-2724-020-4 24 Vdc 2 A
EB-2724-030-0 24 Vdc 3 A
EB-2724-030-4 24 Vdc 3 A
EB-2724-040-0 24 Vdc 4 A
EB-2724-040-4 24 Vdc 4 A
EB-2724-060-0 24 Vdc 6 A
EB-2724-060-4 24 Vdc 6 A
EB-2724-080-0 24 Vdc 8 A
EB-2724-080-4 24 Vdc 8 A
EB-2724-100-0 24 Vdc 10 A
EB-2724-100-4 24 Vdc 10 A
EB-0748-100-0 48 Vdc 0,5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A
EB-1748-060-0 48 Vdc 6 A
EB-1748-100-0 48 Vdc 10 A

Technical Data for EB-2724-040-4

Input
Input rated voltage 24 Vdc
Input voltage range 18 - 30 Vdc
Maximal residual ripple of supplied input voltage 3 %
Max. total input current 4 A
Max. input current for each pole of terminal 10 A (-), 40 A (+)
Required input voltage for turning-on of outputs 17.5 Vdc (Turn-off Threshold 16.7 Vdc),
± 0.7 Vdc
Max. power losses 0,4 W
Over voltage protection Suppressor diode 33 Vdc
Stand-by current 12 mA @ 24 Vdc
Power losses in stand-by mode 0,3 W @ 24 Vdc
Turn on capacity 80 mF @ 24 Vdc / 2,5 mm² / 2,5 m
Output
Output rated voltage 24 Vdc
Maximum voltage drop between input and output 34 mV
Initialization time of module 27 ms
Turn-on delay of outputs 0 ms
Waiting periode after switch-off of an output 500 ms (Short circuit) … 5 s (Overload)
Maximum turn-on capacity for each channel 60 mF
Parallel use of outputs Not allowed
Serial use of outputs not allowed
Resistance to reverse feed max. 35 Vdc
Output rated current 4 A
Efficiency 99 %
Signaling
Bus communication Single notification signal
Status indicator LED (red, green, orange)
Signal output Output status, short circuit proof
high = Channel on, low = Channel off, fault
Approvals
Approvals cURus, cULus, DNV GL
Environment
Type of cooling Natural convection
Ambient temperature -25 °C … +70 °C
Storage temperature -13 °F … +185 °F
Relative humidity 5 … 96 %, without condensation
Required minimum spacing (left/right) 0.00 inch
Required minimum spacing (over/under) 1.18 inch
Safety and protection
Protection index IP 20
Safety class III, without PE connection
Degree of pollution 2
Terminal and mounting
Terminals input, (spring clamp terminal) max. 16 mm²
Terminals output, (spring clamp terminal) max. 2,5 mm² (2 x "+")
Terminals signalling, (spring clamp terminal) max. 2,5 mm²
Mounting position horizontal for
standard rail DIN TS35
Measures and weights
Width 0.47 inch
Height 3.90 inch
Depth 2.36 inch
Weight 0.09 lbs

Information for EasyB 1-Channel thermomagnetic series

General Data
  • Up to 40 fuse channels stackable side by side
  • Protection index IP 20
  • Collective notification signal or single notification signal
  • Thermomagnetic characteristic
  • Ambient temperature -13 °F / -25 °C to +158 °F / 70 °C
  • Multi-coloured LED and status display button
  • Efficiency 99 %
  • 24 Vdc 1-channel circuit breaker system
Benefits
  • Additional load outputs through output expanders mountable sidewise
  • Automatic channel assignment
  • Optional undervoltage shutdown in combined network
  • 3 years warranty

Our recommendations for you

BLOCK product: EB-GND4
EB-GND4
Ground module
0 V paralled terminal with 4 or 8 inputs, Input rated voltage 12/24/48 Vdc, Output rated current max. 40 A
View accessory
BLOCK product: EB-PT2-0
EB-PT2-0
2-pole physical isolation
PRI 24 , SEC 24 Vdc, 6 A
View accessory
BLOCK product: EB-COV
EB-COV
Left side cover
BLOCK product: EB-2824-040-0
EB-2824-040-0
1-Channel circuit breaker current-limiting
Preset tripping current, Active current limiting, 1-Channel, 1 – 10 A
View accessory
BLOCK product: EB-BAR
EB-BAR
Power bus bar
Current capacity up to 80 A, ,
View accessory
BLOCK product: EB-PMM
EB-PMM
Output expander
For mounting on right side of EasyB circuit breaker, 24 Vdc, 24 Vdc, 10 A
View accessory