Autotransformer
VT 35-EN
Characteristics
General data
The autotransformers of the VT-EN series are used for voltage adjustment without the need for galvanic isolation. The transformers feature lower weight and a smaller form factor compared to other transformer types with separate windings and can be easily mounted using robust metal base brackets with elongated holes.
Benefits
› Autotransformer according to EN (IEC) 61558-2-13
› Very high efficiency
› Excellent moisture protection and low noise emission thanks to BLOCK IMPEX vacuum impregnation
› Touch-protected connection terminals according to UVV BGV A3
| Product | Autotransformer | 
| Order number | VT 35-EN | 
| Series | VT-EN | 
| Power | 350 VA | 
| Input | 110 V / 125 V / 230 V / 240 V | 
| Output | 110 V • 3.18 Aac oder 125 V • 2.8 Aac oder 230 V • 1.52 Aac oder 240 V • 1.46 Aac | 
| Phases | 1 | 
| Frequency range | 50 Hz to 60 Hz | 
| Short-Circuit Losses | 10.8 W | 
| No-Load Losses | 7.4 W | 
| EN Insulation class | B (130°C) | 
| UL Insulation class | class 105 | 
| Duty Cycle | 100 % | 
| Wire material | Copper | 
| Efficiency | 95.1 % | 
General
| Short circuit proof | not short-circuit proof | 
| Switching group | Ia0 | 
| Cooling type | AN | 
Environment
| Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F | 
| Max. installation height | 2,000 m / 6,562 ft | 
Protection and Safety
| Protection type | IP00 | 
| Protection class (prepared) | I | 
| Degree of contamination | 1 | 
Electrical Connections
| Input terminal | Screw terminal | 
| Output terminal | Screw terminal | 
| Terminal PE | Flat plug connection | 
Size and Weight
| Width | 87 mm / 3.43 in | 
| Height | 120 mm / 4.72 in | 
| Depth | 105 mm / 4.13 in | 
| Weight | 3.6 kg / 7.937 lbs | 
| Low Voltage Directive | EN 61558-2-13 | 
| Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 | 
 
            
    
                 
         
         
         
        