Control- and isolating transformer
UTT1-2,5-23 - Discontinued items – not for new applications
Characteristics
Benefits
› Safe galvanic isolation
› Patented assembly technology
› Very good corrosion protection and low noise thanks to BLOCK IMPEX vacuum impregnation
› Primary side ±5 % tappings for voltage adjustment
› Fixed, contact protected screw connection terminals complying with UVV BGV A3
› Multifunctional fixing rail with 8 oval slots
› Space saving, thanks to horizontal design
› Integrated crane eyes
› Non-slip terminals
| Product | Control- and isolating transformer |
| Order number | UTT1-2,5-23 |
| Series | TT1 |
| Power | 2,500 VA |
| Input | 208 V / 230 V / 380 V / 400 V / 415 V / 440 V / 460 V / 480 V / 500 V / 525 V / 550 V / 575 V / 600 V |
| Output | 2 x 115 V • 10.86 Aac |
| Phases | 1 |
| Frequency range | 50 Hz to 60 Hz |
| Short-Circuit Losses | 163 W |
| No-Load Losses | 37 W |
| Short-Term Power / instantaneous output | 6,333 VA |
| EN Insulation class | F (155°C) |
| UL Insulation class | class 155 |
| Duty Cycle | 100 % |
| Wire material | Copper |
| Efficiency | 92.6 % |
General
| Short circuit proof | not short-circuit proof |
| Switching group | II |
| Cooling type | AN |
Environment
| Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
| Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
| Protection type | IP00 |
| Protection class (prepared) | I |
| Overvoltage category | III |
| Degree of contamination | 1 |
Electrical Connections
| Input terminal | Screw terminal |
| Output terminal | Screw terminal |
| Terminal PE | Screw terminal |
Size and Weight
| Weight | 36 kg / 79.366 lbs |
| Low Voltage Directive |
EN 61558-2-2 EN 61558-2-4 |
| RoHS compliant | EN IEC 63000 |
| Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |