Control- and isolating transformer
USTE 160/2x115 - Discontinued items – not for new applications
Characteristics
Benefits
› Universal input voltages 208 to 600 Vac
› Very good switch-on behaviour thanks to reduced starting currents
› High power density due to a compact construction design
› Very good corrosion protection and low noise thanks to BLOCK IMPEX vacuum impregnation
› Quick to cable up thanks to the use of spring-clamp terminals
› Contact protected screw connection terminals complying with UVV BGV A3
› Simple mounting thanks to robust metal footplate with oval slots
› With combination footplate for bolted and rail mounting
| Product | Control- and isolating transformer |
| Order number | USTE 160/2x115 |
| Series | USTE |
| Power | 160 VA |
| Input | 208 V / 230 V / 380 V / 400 V / 415 V / 440 V / 460 V / 480 V / 500 V / 525 V / 550 V / 575 V / 600 V |
| Output | 2 x 115 V • 0.69 Aac |
| Phases | 1 |
| Frequency range | 50 Hz to 60 Hz |
| Short-Circuit Losses | 16.6 W |
| No-Load Losses | 6.14 W |
| Short-Term Power / instantaneous output | 350 VA |
| EN Insulation class | B (130°C) |
| UL Insulation class | class 130 |
| Duty Cycle | 100 % |
| Wire material | Copper |
| Efficiency | 87.6 % |
General
| Short circuit proof | not short-circuit proof |
| Switching group | IIii0 |
| Cooling type | AN |
Environment
| Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
| Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
| Protection type | IP00 |
| Protection class (prepared) | I |
| Overvoltage category | III |
| Degree of contamination | 1 |
Electrical Connections
| Input terminal | Push-in terminal |
| Output terminal | Push-in terminal |
| Terminal PE | Flat plug connection |
Size and Weight
| Weight | 2.85 kg / 6.283 lbs |
General
| TS35 rail mounting possible | Ja |
| Low Voltage Directive |
EN 61558-2-2 EN 61558-2-4 |
| Approval cULus - Listed | UL 5085-1/-2; CSA 22.2 |