Control- and isolating transformer
STU 630/2x115
Characteristics
Benefits
› Universal input voltages 210 to 540 Vac
› Very good switch-on behaviour thanks to reduced starting currents
› High power density due to a compact construction design
› Very good corrosion protection and low noise thanks to BLOCK IMPEX vacuum impregnation
› Contact protected screw connection terminals complying with UVV BGV A3
› Simple mounting thanks to robust metal footplate with oval slots
Product | Control- and isolating transformer |
Order number | STU 630/2x115 |
Power | 630 VA |
UL Derating | 500.00 VA |
Input | 230 V / 400 V / 460 V / 520 V ± 20 V |
Output | 2 x 115 V • 2.74 Aac |
Phases | 1 |
Frequency range | 50 Hz to 60 Hz |
Short-Circuit Losses | 35 W |
No-Load Losses | 18 W |
Short-Term Power / instantaneous output | 1,540 VA |
Short circuit voltage uk | 5.2 % |
EN insulation class | B (130°C) |
UL Insulation class | class 105 |
Duty Cycle | 100 % |
Wire material | Copper |
Efficiency | 92.2 % |
General
Short circuit proof | not short-circuit proof |
Switching group | Iii0 |
Cooling type | AN |
Environment
Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F |
Max. installation height | 2,000 m / 6,562 ft |
Protection and Safety
Protection type | IP 00 |
Protection class (prepared) | I |
Overvoltage category | III |
Degree of contamination | 2 |
Electrical Connections
Input terminal | Screw terminal |
Output terminal | Screw terminal |
Terminal PE | Flat plug connection |
Size and Weight
Width | 150 mm / 5.91 in |
Height | 149 mm / 5.87 in |
Depth | 112 mm / 4.41 in |
Weight | 8 kg / 17.64 lbs |
Low Voltage Directive |
EN 61558-2-2 EN 61558-2-4 |
Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 |
VDE Approval |
VDE 0570-2-x (DIN EN 61558-2-x) |