Control- and isolating transformer
ST 2000/11/23 - Discontinued types – not for new designs
Characteristics
Benefits
› Very good switch-on behaviour thanks to reduced starting currents
› High power density due to a compact construction design
› Primary side ±5 % tappings for voltage adjustment
› Very good corrosion protection and low noise thanks to BLOCK IMPEX vacuum impregnation
› Contact protected screw connection terminals complying with UVV BGV A3
› Simple mounting thanks to robust metal footplate with oval slots
| Product | Control- and isolating transformer | 
| Order number | ST 2000/11/23 | 
| Series | ST | 
| Power | 2,000 VA | 
| Input | 109 V / 115 V / 121 V | 
| Output | 230 V • 8.69 Aac | 
| Phases | 1 | 
| Frequency range | 50 Hz to 60 Hz | 
| Short-Circuit Losses | 71 W | 
| No-Load Losses | 45 W | 
| Short-Term Power / instantaneous output | 5,640 VA | 
| Short circuit voltage uk | 2.8 % | 
| EN Insulation class | B (130°C) | 
| UL Insulation class | class 130 | 
| Duty Cycle | 100 % | 
| Wire material | Copper | 
| Efficiency | 94.5 % | 
General
| Short circuit proof | not short-circuit proof | 
| Switching group | Ii0 | 
| Cooling type | AN | 
Environment
| Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F | 
| Max. installation height | 2,000 m / 6,562 ft | 
Protection and Safety
| Protection type | IP00 | 
| Protection class (prepared) | I | 
| Overvoltage category | III | 
| Degree of contamination | 2 | 
Electrical Connections
| Input terminal | Screw terminal | 
| Output terminal | Screw terminal | 
| Terminal PE | Flat plug connection | 
Size and Weight
| Weight | 21 kg / 46.297 lbs | 
| Low Voltage Directive | EN 61558-2-2 EN 61558-2-4 | 
| Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 | 
 
            
    
                 
            
    
                 
             
            