Toroidal transformers, isolating transformer
RTE 80/2x24
Characteristics
General data
The toroidal transformers of the RTE series enable space-saving use due to minimal size with maximum performance. The transformers feature overload protection thanks to the built-in thermal fuse and have a lightweight design. The connections can be soldered directly onto a PCB.
Benefits
› Isolating transformer according to EN (IEC) 61558-2-4
› Dual output coils for series or parallel connection
› Minimal no-load losses
› Excellent temperature behavior due to low magnetic stray field
› Very low noise field
| Product | Toroidal transformers, isolating transformer | 
| Order number | RTE 80/2x24 | 
| Series | RTE | 
| Power | 80 VA | 
| Input | 230 V | 
| Output | 2 x 24 V • 1.67 Aac | 
| Phases | 1 | 
| Frequency range | 50 Hz to 60 Hz | 
| Short-Circuit Losses | 11.2 W | 
| No-Load Losses | 1 W | 
| Short circuit voltage uk | 11.3 % | 
| EN Insulation class | B (130°C) | 
| UL Insulation class | class 105 | 
| Duty Cycle | 100 % | 
| Wire material | Copper | 
| Efficiency | 86.8 % | 
General
| Short circuit proof | not short-circuit proof | 
| Switching group | Iii0 | 
| Cooling type | AN | 
Environment
| Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F | 
| Max. installation height | 2,000 m / 6,562 ft | 
Protection and Safety
| Protection type | IP00 | 
| Protection class (prepared) | II | 
| Overvoltage category | III | 
| Degree of contamination | 2 | 
Electrical Connections
| Input terminal | Stranded wire | 
| Output terminal | Wire connection | 
Size and Weight
| Weight | 0.992 kg / 2.187 lbs | 
| Low Voltage Directive | EN 61558-2-4 | 
| Approval cURus - Recognized | UL 5085-1/-2; CSA 22.2 | 
 
            
    
                 
            
    
                 
             
             
             
        