PM-0724-200-0
Electronic circuit breaker with thermomagnetic characteristic ECONOMY SMART
Input rated voltage
24 Vdc
Output rated current
2 x 2 - 10 A, adjustable
Characteristics
-
Version | Input rated voltage | Output rated current | Characteristics | |
---|---|---|---|---|
PM-0712-200-0 | 12 Vdc | 2 x 2 - 10 A, adjustable | - | |
PM-0712-400-0 | 12 Vdc | 4 x 2 - 10 A, adjustable | - | |
PM-0724-120-0 | 24 Vdc | 2 x 1 - 6 A, adjustable | - | |
PM-0724-200-0 | 24 Vdc | 2 x 2 - 10 A, adjustable | - | |
PM-0724-240-0 | 24 Vdc | 4 x 1 - 6 A, adjustable | - | |
PM-0724-400-0 | 24 Vdc | 4 x 2 - 10 A, adjustable | - | |
PM-0724-400-2 | 24 Vdc | 4 x 2 - 10 A, adjustable | Potential-free signal output | |
PM-0724-400-0I1 | 24 Vdc | 4 x 1 - 10 A, adjustable | IO-Link interface | |
PM-0748-200-0 | 48 Vdc | 2 x 2 - 10 A, adjustable | - | |
PM-0748-200-2 - no longer available | 48 Vdc | 2 x 2 - 10 A, adjustable | Potential-free signal output | |
PM-0748-400-0 | 48 Vdc | 4 x 2 - 10 A, adjustable | - | |
PM-0748-400-2 | 48 Vdc | 4 x 2 - 10 A, adjustable | Potential-free signal output | |
PC-0724-480-0 | 24 Vdc | 8 x 1 - 6 A, adjustable | - | |
PC-0724-800-0 | 24 Vdc | 8 x 2 - 10 A, adjustable | - | |
PC-0724-800-0I1 | 24 Vdc | 8 x 1 - 10 A, adjustable | IO-Link interface | |
PC-0724-800-2 | 24 Vdc | 8 x 2 - 10 A, adjustable | Potential-free signal output | |
PC-0748-800-0 | 48 Vdc | 8 x 2 - 10 A, adjustable | - | |
PC-0748-800-2 | 48 Vdc | 8 x 2 - 10 A, adjustable | Potential-free signal output |
DOWNLOADS
Technical files
Manual
Instruction manual
Dimension sheet
Approvals / Manufacturer's declaration
UL 508 Listed USA (E219022)
UL 508 Listed Canada (E219022)
COC UL 508 & CSA 22.2
UL 2367 USA (E356250)
COA UL 2367 & CSA 22.2
COC UL 2367 & CSA 22.2
Marine DNV GL (TAA00001S5)
EAC approval
EU-Declaration of Conformity
CAD/CAE data
3D-CAD-Model (STEP)
Software
PLC sample program (function) for TIA
PLC sample program (function) for TIA V13
PLC sample program (function) for TIA V13 CPU1200
PLC sample program (function) for TIA_V14_CPU1200
PLC sample program (function) for Step 7 (created with version 5.4)
CODESYS function block
Communication protocol 2-wire interface
Additional information
eBreaker brochure
Product Change Notification Lateral Mounting
Technical data for PM-0724-200-0
Special features | |
---|---|
Characteristics | - |
Input | |
---|---|
Input rated voltage | 24 Vdc |
Input voltage range | 18 - 30 Vdc |
Maximal residual ripple of supplied input voltage | 3 % |
Required input voltage for turning-on of outputs | 19.5 Vdc (Turn-off Threshold 18 Vdc) |
Max. total input current | 20 A |
Max. input current for each pole of terminal | 40 A |
Over voltage protection | Suppressor diode 33 Vdc |
Stand-by current | 35 mA @ 24 Vdc |
Power losses in stand-by mode | 0.84 W @ 24 Vdc |
Output | |
---|---|
Output rated voltage | 24 Vdc |
Output rated current | 2 x 2 - 10 A, adjustable |
Maximum voltage drop between input and output | 200 mV @ 2 x 10 A |
Initialization time of module | 250 ms |
Turn-on delay of outputs | Load dependent, min. 50 ms / max. 5 s |
Waiting periode after switch-off of an output | 500 ms (short circuit) ... 10 s (overload) |
Efficiency | 99.0 % |
Max. power losses | 5.5 W @ 2 x 10 A |
Maximum turn-on capacity for each channel | min. 63 mF @ 24 Vdc / 2.5 mm² / 2.5 m |
Internal output fuse | 15 A |
Resistance to reverse feed max. | 35 Vdc |
Parallel use of outputs | Not allowed |
Serial use of outputs | Not allowed |
Signaling | |
---|---|
Status indicator | LED (red, green, orange) |
Signal input S1 | 24 Vdc (On/Off/Reset) |
Signal output S2 | 24 Vdc, max. 25 mA (status output channels) |
Signal output S3 | 24 Vdc, max. 25 mA (Common signalling output) |
Approvals | |
---|---|
Approvals | cURus, cULus, DNV GL |
Environment | |
---|---|
Storage temperature | -25 °C to +85 °C |
Ambient temperature | -25 °C to +70 °C |
Derating | - |
Type of cooling | Natural convection |
Required minimum spacing (left/right) | 0 mm |
Required minimum spacing (over/under) | 40 mm |
Safety and protection | |
---|---|
Protection index | IP 20 |
Safety class | III, without PE connection |
Degree of pollution | 2 |
Terminal and mounting | |
---|---|
Mounting position | horizontal for standard rail DIN TS35 |
Input terminals (2 x "-"), 1) direct plug-in technology Push-in | max. 2,5 mm² |
Input terminals (2 x "+"), 1) direct plug-in technology Push-in | max. 6 mm² |
Terminals signalling (direct plug-in technology Push-in) | max. 2,5 mm² |
Output terminals ("+"), direct plug-in technoligy Push-in | max. 2,5 mm² |
Measures and weights | |
---|---|
Width | 45 mm |
Height | 90 mm |
Depth | 91.5 mm |
Weight | 0.20 kg |
Info on ECONOMY SMART series
General Data
- Thermomagnetic characteristic
- Efficiency typ. 99 %
- Protection index IP 20
- Ambient temperature -25 °C to +70 °C
- Nominal input voltage 12 / 24 / 48 Vdc
- Tripping current 1 - 6 A / 1 - 10 A / 2 - 10 A
- Output channels 2 / 4 / 8
Benefits
- LED signalisation and remote request for each output channel
- Sequential and load-dependent switching-on of channels
- Adjustable tripping current for each output channel via current selector switch
- Ability to turn-on high load capacitance at each channel
- Comprehensive single-channel-diagnostics and remote switching on/off of each output channel via 2-wire-interface, potential-free signal output or IO-Link
- Group alarm contact
- 3 years warranty