PM-0724-120-0

Electronic circuit breaker with thermomagnetic characteristic ECONOMY SMART

Version PM-0724-120-0
Input rated voltage 24 Vdc Output rated current 2 x 1 - 6 A, adjustable Characteristics -
Version Input rated voltage Output rated current Characteristics
PM-0712-200-0 12 Vdc 2 x 2 - 10 A, adjustable -
PM-0712-400-0 12 Vdc 4 x 2 - 10 A, adjustable -
PM-0724-120-0 24 Vdc 2 x 1 - 6 A, adjustable -
PM-0724-200-0 24 Vdc 2 x 2 - 10 A, adjustable -
PM-0724-240-0 24 Vdc 4 x 1 - 6 A, adjustable -
PM-0724-400-0 24 Vdc 4 x 2 - 10 A, adjustable -
PM-0724-400-2 24 Vdc 4 x 2 - 10 A, adjustable Potential-free signal output
PM-0724-400-0I1 24 Vdc 4 x 1 - 10 A, adjustable IO-Link interface
PM-0748-200-0 48 Vdc 2 x 2 - 10 A, adjustable -
PM-0748-200-2 - no longer available 48 Vdc 2 x 2 - 10 A, adjustable Potential-free signal output
PM-0748-400-0 48 Vdc 4 x 2 - 10 A, adjustable -
PM-0748-400-2 48 Vdc 4 x 2 - 10 A, adjustable Potential-free signal output
PC-0724-480-0 24 Vdc 8 x 1 - 6 A, adjustable -
PC-0724-800-0 24 Vdc 8 x 2 - 10 A, adjustable -
PC-0724-800-0I1 24 Vdc 8 x 1 - 10 A, adjustable IO-Link interface
PC-0724-800-2 24 Vdc 8 x 2 - 10 A, adjustable Potential-free signal output
PC-0748-800-0 48 Vdc 8 x 2 - 10 A, adjustable -
PC-0748-800-2 48 Vdc 8 x 2 - 10 A, adjustable Potential-free signal output

Technical data for PM-0724-120-0

Special features
Characteristics -
Input
Input rated voltage 24 Vdc
Input voltage range 18 - 30 Vdc
Maximal residual ripple of supplied input voltage 3 %
Required input voltage for turning-on of outputs 19.5 Vdc (Turn-off Threshold 18 Vdc)
Max. total input current 12 A
Max. input current for each pole of terminal 40 A
Over voltage protection Suppressor diode 33 Vdc
Stand-by current 35 mA @ 24 Vdc
Power losses in stand-by mode 0.84 W @ 24 Vdc
Output
Output rated voltage 24 Vdc
Output rated current 2 x 1 - 6 A, adjustable
Maximum voltage drop between input and output 120 mV @ 2 x 6 A
Initialization time of module 250 ms
Turn-on delay of outputs Load dependent, min. 50 ms / max. 5 s
Waiting periode after switch-off of an output 500 ms (short circuit) ... 10 s (overload)
Efficiency 99.0 %
Max. power losses 2.5 W @ 2 x 6 A
Maximum turn-on capacity for each channel min. 63 mF @ 24 Vdc / 2.5 mm² / 2.5 m
Internal output fuse 15 A
Resistance to reverse feed max. 35 Vdc
Parallel use of outputs Not allowed
Serial use of outputs Not allowed
Signaling
Status indicator LED (red, green, orange)
Signal input S1 24 Vdc (On/Off/Reset)
Signal output S2 24 Vdc, max. 25 mA
(status output channels)
Signal output S3 24 Vdc, max. 25 mA
(Common signalling output)
Approvals
Approvals cURus, cULus, DNV GL
Environment
Storage temperature -25 °C to +85 °C
Ambient temperature -25 °C to +70 °C
Derating -
Type of cooling Natural convection
Required minimum spacing (left/right) 0 mm
Required minimum spacing (over/under) 40 mm
Safety and protection
Protection index IP 20
Safety class III, without PE connection
Degree of pollution 2
Terminal and mounting
Mounting position horizontal for standard rail DIN TS35
Input terminals (2 x "-"), 1) direct plug-in technology Push-in max. 2,5 mm²
Input terminals (2 x "+"), 1) direct plug-in technology Push-in max. 6 mm²
Terminals signalling (direct plug-in technology Push-in) max. 2,5 mm²
Output terminals ("+"), direct plug-in technoligy Push-in max. 2,5 mm²
Measures and weights
Width 45 mm
Height 90 mm
Depth 91.5 mm
Weight 0.20 kg

Info on ECONOMY SMART series

General Data
  • Thermomagnetic characteristic
  • Efficiency typ. 99 %
  • Protection index IP 20
  • Ambient temperature -25 °C to +70 °C
  • Nominal input voltage 12 / 24 / 48 Vdc
  • Tripping current 1 - 6 A / 1 - 10 A / 2 - 10 A
  • Output channels 2 / 4 / 8
Benefits
  • LED signalisation and remote request for each output channel
  • Sequential and load-dependent switching-on of channels
  • Adjustable tripping current for each output channel via current selector switch
  • Ability to turn-on high load capacitance at each channel
  • Comprehensive single-channel-diagnostics and remote switching on/off of each output channel via 2-wire-interface, potential-free signal output or IO-Link
  • Group alarm contact