Safety isolating transformer
EL 7,5/18 - Discontinued types – not for new designs
Characteristics
General data
The safety transformers of the EL series provide safe galvanic isolation of the primary circuit from the secondary circuit and are manufactured according to EN (IEC) 61558-2-6. By limiting the output voltage, the transformers are suitable for the construction of SELV and PELV circuits.
Benefits
› Solder connection for free wiring
› With dual output coils for series and parallel connection
› Excellent corrosion protection and low noise emission thanks to BLOCK IMPEX vacuum impregnation
› Easy mounting with a sturdy metal base plate featuring elongated holes
| Product | Safety isolating transformer | 
| Order number | EL 7,5/18 | 
| Series | EL | 
| Power | 7.5 VA | 
| Input | 230 V | 
| Output | 2 x 18 V • 0.208 Aac | 
| Phases | 1 | 
| Frequency range | 50 Hz to 60 Hz | 
| No-Load Losses | 2 W | 
| EN Insulation class | E (120°C) | 
| Duty Cycle | 100 % | 
| Wire material | Copper | 
| Efficiency | 62 % | 
General
| Short circuit proof | not short-circuit proof | 
| Switching group | Iii0 | 
| Cooling type | AN | 
Environment
| Ambient temperature | -20 °C to 40 °C / -4 °F to 104 °F | 
| Max. installation height | 2,000 m / 6,562 ft | 
Protection and Safety
| Protection type | IP00 | 
| Protection class (prepared) | II | 
| Overvoltage category | III | 
| Degree of contamination | 2 | 
Electrical Connections
| Input terminal | Soldering eye | 
| Output terminal | Soldering eye | 
Size and Weight
| Width | 39 mm / 1.54 in | 
| Height | 45 mm / 1.77 in | 
| Depth | 48 mm / 1.89 in | 
| Weight | 0.256 kg / 0.564 lbs | 
| Low Voltage Directive | EN 61558-2-6 |