EB-0724-100-0F

1-Channel circuit breaker thermomagnetic, EasyB

Version EB-0724-100-0F
Input rated voltage 24 Vdc Output rated current 0.5 - 10 A, adjustable (0,5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A)
Version Input rated voltage Output rated current
EB-0724-100-0F 24 Vdc 0.5 - 10 A, adjustable (0,5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A)
EB-1724-010-0F 24 Vdc 1 A, NEC Class 2
EB-1724-020-0F 24 Vdc 2 A, NEC Class 2
EB-1724-030-0F 24 Vdc 3 A, NEC Class 2
EB-1724-040-0F 24 Vdc 4 A, NEC Class 2
EB-1724-060-0F 24 Vdc 6 A
EB-1724-080-0F 24 Vdc 8 A
EB-1724-100-0F 24 Vdc 10 A
EB-1724-160-0F 24 Vdc 16 A
EB-3724-100-0F 24 Vdc 0.5 - 10 A, adjustable (0,5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A)
Image of %s BLOCK Item: EB-0724-100-0F
Technical files Instruction manual Approvals / Manufacturer's declaration EU-Declaration of Conformity

Technical data for EB-0724-100-0F

Input
Input rated voltage 24 Vdc
Input voltage range 18 - 30 Vdc
Maximal residual ripple of supplied input voltage 3 %
Max. total input current 10 A
Max. input current for each pole of terminal 10 A (-), 40 A (+)
Required input voltage for turning-on of outputs 17.5 Vdc (Turn-off Threshold 16.7 Vdc),
± 0.7 Vdc
Max. power losses 3,3 W
Over voltage protection Suppressor diode 33 Vdc
Power losses in stand-by mode 0,3 W
Turn on capacity 60 mF @ 24 Vdc/ 2,5 mm²/2,5 m
Output
Output rated voltage 24 Vdc
Initialization time of module 52 ms
Turn-on delay of outputs min. 50 ms / max. 5 s
Waiting periode after switch-off of an output 500 ms (Short circuit) … 5 s (Overload)
Maximum turn-on capacity for each channel 60 mF
Parallel use of outputs Not allowed
Serial use of outputs not allowed
Resistance to reverse feed max. 35 Vdc
Output rated current 0.5 - 10 A, adjustable (0,5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A)
Efficiency 99.0 %
Signaling
Bus communication Read:-state (tripped, On, Off)
-set/active current
-input voltage
-firmware version/serial number
Write:-state (on, off, reset)
Status indicator LED (red, green, orange)
Signal output Output status, short circuit proof
high = Channel on, low = Channel off, fault
Signal output (ON/OFF/Reset) Reset input
Level high = min. 15 Vdc, max. 30 Vdc
Level low = min. 0 Vdc, max. 5 Vdc
Approvals
Approvals cURus, cULus
Environment
Type of cooling Natural convection
Ambient temperature -25 °C … +70 °C
Storage temperature -25 °C … +85 °C
Derating 10A +55°C, <10A +60°C, <6A +70°C
Relative humidity 5 … 96 %, without condensation
Required minimum spacing (left/right) 0 mm
Required minimum spacing (over/under) 30 mm
Safety and protection
Protection index IP 20
Safety class III, without PE connection
Degree of pollution 2
Terminal and mounting
Terminals input, (spring clamp terminal) max. 16 mm²
Terminals output, (spring clamp terminal) max 2,5 mm² (1 x "+")
Terminals signalling, (spring clamp terminal) max. 2,5 mm²
Mounting position horizontal for
standard rail DIN TS35
Measures and weights
Weight 0.039 kg
Width 12 mm
Height 99.3 mm
Depth 64.5 mm

Info on EasyB 1-Channel thermomagnetic, adjusted internal fuse, communicative series

General Data
  • Protection index IP 20
  • Efficiency up to 99 %
  • 24 Vdc 1-channel circuit breaker system
  • Ambient temperature -25 °C to +70 °C
  • Collective notification signal
  • Thermomagnetic characteristic
  • Multi-coloured LED and status display button
  • Up to 40 fuse channels stackable side by side
Benefits
  • Internal fuse adapted to the tripping current
  • Automatic channel assignment
  • 3 years warranty
  • Undervoltage shutdown per channel
  • Additional load outputs through output expanders mountable sidewise