STEU 630/48

Control- and isolating transformer

Version STEU 630/48
Rated input voltage 230/400 Vac Rated output voltage 2 x 24 Vac Rated power VDE (DB cos phi=1) 630 VA
Version Rated input voltage Rated output voltage Rated power VDE (DB cos phi=1)
STEU 20/23 230/400 Vac 2 x 115 Vac 20 VA
STEU 20/24 230/400 Vac 2 x 12 Vac 20 VA
STEU 63/24 230/400 Vac 2 x 12 Vac 63 VA
STEU 63/48 230/400 Vac 2 x 24 Vac 63 VA
STEU 63/23 230/400 Vac 2 x 115 Vac 63 VA
STEU 100/24 230/400 Vac 2 x 12 Vac 100 VA
STEU 100/48 230/400 Vac 2 x 24 Vac 100 VA
STEU 100/23 230/400 Vac 2 x 115 Vac 100 VA
STEU 160/24 230/400 Vac 2 x 12 Vac 160 VA
STEU 160/48 230/400 Vac 2 x 24 Vac 160 VA
STEU 160/23 230/400 Vac 2 x 115 Vac 160 VA
STEU 250/24 230/400 Vac 2 x 12 Vac 250 VA
STEU 250/48 230/400 Vac 2 x 24 Vac 250 VA
STEU 250/23 230/400 Vac 2 x 115 Vac 250 VA
STEU 320/24 230/400 Vac 2 x 12 Vac 320 VA
STEU 320/48 230/400 Vac 2 x 24 Vac 320 VA
STEU 320/23 230/400 Vac 2 x 115 Vac 320 VA
STEU 400/24 230/400 Vac 2 x 12 Vac 400 VA
STEU 400/48 230/400 Vac 2 x 24 Vac 400 VA
STEU 400/23 230/400 Vac 2 x 115 Vac 400 VA
STEU 500/24 230/400 Vac 2 x 12 Vac 500 VA
STEU 500/48 230/400 Vac 2 x 24 Vac 500 VA
STEU 500/23 230/400 Vac 2 x 115 Vac 500 VA
STEU 630/24 230/400 Vac 2 x 12 Vac 630 VA
STEU 630/23 230/400 Vac 2 x 115 Vac 630 VA
STEU 630/48 230/400 Vac 2 x 24 Vac 630 VA
STEU 800/24 230/400 Vac 2 x 12 Vac 800 VA
STEU 800/48 230/400 Vac 2 x 24 Vac 800 VA
STEU 800/23 230/400 Vac 2 x 115 Vac 800 VA
STEU 1000/24 230/400 Vac 2 x 12 Vac 1,000 VA
STEU 1000/48 230/400 Vac 2 x 24 Vac 1,000 VA
STEU 1000/23 230/400 Vac 2 x 115 Vac 1,000 VA
STEU 1600/23 230/400 Vac 2 x 115 Vac 1,600 VA
STEU 2000/23 230/400 Vac 2 x 115 Vac 2,000 VA
STEU 2500/23 230/400 Vac 2 x 115 Vac 2,500 VA
Image of BLOCK Item: STEU 630/48
Technical files Data sheet CAD/CAE data 3D-CAD-Model (STEP) ePlan Makro

Technical Data for STEU 630/48

Input
Rated input voltage 230/400 Vac
Tappings Input ±15 V
Rated frequency 50 - 60 Hz
Output
Rated output voltage 2 x 24 Vac
Rated power VDE (DB cos phi=1) 630 VA
Rated power VDE (KB cos phi=0.5) 2.350 VA
No-load voltage (app. x factor) 1.03
Efficiency 92 %
Standards
Classification Control- and isolating transformer
Approvals
Approvals cURus
Environment
Ambient temperature max. 104.0 °F
Type of cooling self-cooling
Safety and protection
Type Open type
Insulation class VDE=B, UL=class 130
Protection index IP 00
Safety class (prepared) I
Short circuit strength non-short-circuit proof
PRI Fusing recommendation by circuit breaker with tripping characteristic type 20 x Irated related to set)
Setting range 230 ±15 Vac 2.50 - 4.00 A
Setting value 230 ±15 Vac 3 A
Setting range 400 ±15 Vac 1.60 - 2.50 A
Setting value 400 ±15 Vac 1.7 A
Terminal and mounting
Fixing method Base plate
Fixing screws M6
Terminals Input push-in terminals, 4 mm²
Terminals Output push-in terminals, 4 mm²
Connection type Tab connector, 6.3 x 0.8 mm
Measures and weights
Depth 4.69 inch
Height 5.75 inch
Width 5.91 inch
Weight 17.42 lbs

Information for STEU series

General Data
  • Insulation class B
  • Degree of protection IP 00
  • Efficiency up to 94 %
  • Maximum ambient temperature 104 °F / 40 °C
  • Rated power 63 - 2,500 VA
  • Rated output voltage 24 - 230 Vac
  • Rated input voltage 230 and 400 Vac
Benefits
  • Fast installation because of the use of push-in terminals
  • High power density due to a compact construction design
  • Dual input voltage 230 and 400 Vac
  • Reduced inrush current
  • Very good corrosion protection and low noise due to BLOCK IMPEX vacuum impregnation
  • Contact protected screw connection terminals complying with UVV BGV A3
  • Simple mounting due to robust metal footplate with oval slots
  • Primary side ±15 V taps for voltage adjustment
  • DIN rail clamp included up to 250 VA