MDB 400/176
Motor reactor MDB
Version MDB 400/176
Rated voltage
3 x 400 Vac
Rated current
176 A
for motor rated output approx.
120.69 HP
Version | Rated voltage | Rated current | for motor rated output approx. | |
---|---|---|---|---|
MDB 400/6,3 | 3 x 400 Vac | 6.3 A | 2.95 HP | |
MDB 400/9,4 | 3 x 400 Vac | 9.4 A | 5.36 HP | |
MDB 400/13 | 3 x 400 Vac | 13 A | 7.38 HP | |
MDB 400/16 | 3 x 400 Vac | 16 A | 10.06 HP | |
MDB 400/24 | 3 x 400 Vac | 24 A | 14.75 HP | |
MDB 400/30 | 3 x 400 Vac | 30 A | 20.12 HP | |
MDB 400/39 | 3 x 400 Vac | 39 A | 24.81 HP | |
MDB 400/46 | 3 x 400 Vac | 46 A | 29.50 HP | |
MDB 400/61 | 3 x 400 Vac | 61 A | 40.23 HP | |
MDB 400/72 | 3 x 400 Vac | 72 A | 49.62 HP | |
MDB 400/91 | 3 x 400 Vac | 91 A | 60.34 HP | |
MDB 400/110 | 3 x 400 Vac | 110 A | 73.76 HP | |
MDB 400/150 | 3 x 400 Vac | 150 A | 100.58 HP | |
MDB 400/176 | 3 x 400 Vac | 176 A | 120.69 HP |
Technical Data for MDB 400/176
Operating data | |
---|---|
Rated voltage | 3 x 400 Vac |
Voltage range | 3 x 0 - 500 Vac |
Rated current | 176 A |
for motor rated output approx. | 120.69 HP |
Inductance | 0.05 mH |
Rated frequency | 0 - 120 Hz |
Switching frequency | 2 - 6 kHz |
Environment | |
---|---|
Ambient temperature max. | 104.0 °F |
Safety and protection | |
---|---|
Type | Open type |
Insulation class | F |
Protection index | IP 00 |
Safety class (prepared) | I |
Test voltage | 2500 Vac, 50 Hz |
Terminal and mounting | |
---|---|
Terminals phase | Flat copper |
Connection type | Bolt, M8 |
Fixing method | Fixing rail |
Fixing screws | M8 |
Measures and weights | |
---|---|
Width | 9.45 inch |
Height | 8.07 inch |
Depth | 6.50 inch |
Weight | 60.63 lbs |
Information for MDB series
General Data
- Rated frequency from 0 to 120 Hz
- Rated voltage 3 x 400 Vac
- Rated current 6.3 - 176 A
- For motor rated output 2.2 - 90 kW
- For switching frequencies of 2 to 6 kHz
- Insulation class F
- Maximum ambient temperature 40 °C
- Degree of protection IP 00
Benefits
- High damping of edge steepness
- High efficiency
- Long shielded cable lengths possible
- High damping of inverter switching frequency
- Very good corrosion protection and low noise due to vacuum impregnation
- Reduction of leakage current