LR3-AE250-485-0

Line reactor LR3-A

Version LR3-AE250-485-0
Rated voltage 3 x 480 Vac Rated current 3 x 250 A Short circuit voltage uK 5 % @ 480 Vac
Version Rated voltage Rated current Short circuit voltage uK
LR3-AD004-404-0 3 x 400 Vac 3 x 4 A 4 % @ 400 Vac
LR3-AD006-404-0 3 x 400 Vac 3 x 6 A 4 % @ 400 Vac
LR3-AD008-404-0 3 x 400 Vac 3 x 8 A 4 % @ 400 Vac
LR3-AD010-404-0 3 x 400 Vac 3 x 10 A 4 % @ 400 Vac
LR3-AD016-404-0 3 x 400 Vac 3 x 16 A 4 % @ 400 Vac
LR3-AD020-404-0 3 x 400 Vac 3 x 20 A 4 % @ 400 Vac
LR3-AD025-404-0 3 x 400 Vac 3 x 25 A 4 % @ 400 Vac
LR3-AD030-404-0 3 x 400 Vac 3 x 30 A 4 % @ 400 Vac
LR3-AD035-404-0 3 x 400 Vac 3 x 35 A 4 % @ 400 Vac
LR3-AD040-404-0 3 x 400 Vac 3 x 40 A 4 % @ 400 Vac
LR3-AD045-404-0 3 x 400 Vac 3 x 45 A 4 % @ 400 Vac
LR3-AD050-404-0 3 x 400 Vac 3 x 50 A 4 % @ 400 Vac
LR3-AD063-404-0 3 x 400 Vac 3 x 63 A 4 % @ 400 Vac
LR3-AE063-404-0 3 x 400 Vac 3 x 63 A 4 % @ 400 Vac
LR3-AD080-404-0 3 x 400 Vac 3 x 80 A 4 % @ 400 Vac
LR3-AE080-404-0 3 x 400 Vac 3 x 80 A 4 % @ 400 Vac
LR3-AE100-404-0 3 x 400 Vac 3 x 100 A 4 % @ 400 Vac
LR3-AE125-404-0 3 x 400 Vac 3 x 125 A 4 % @ 400 Vac
LR3-AE160-404-0 3 x 400 Vac 3 x 160 A 4 % @ 400 Vac
LR3-AE200-404-0 3 x 400 Vac 3 x 200 A 4 % @ 400 Vac
LR3-AE250-404-0 3 x 400 Vac 3 x 250 A 4 % @ 400 Vac
LR3-AE315-404-0 3 x 400 Vac 3 x 315 A 4 % @ 400 Vac
LR3-AE400-404-0 3 x 400 Vac 3 x 400 A 4 % @ 400 Vac
LR3-AE500-404-0 3 x 400 Vac 3 x 500 A 4 % @ 400 Vac
LR3-AE630-404-0 3 x 400 Vac 3 x 630 A 4 % @ 400 Vac
LR3-AE710-404-0 3 x 400 Vac 3 x 710 A 4 % @ 400 Vac
LR3-AE900-404-0 3 x 400 Vac 3 x 900 A 4 % @ 400 Vac
LR3-AE063-483-0 3 x 480 Vac 3 x 63 A 3 % @ 480 Vac
LR3-AE063-485-0 3 x 480 Vac 3 x 63 A 5 % @ 480 Vac
LR3-AE080-483-0 3 x 480 Vac 3 x 80 A 3 % @ 480 Vac
LR3-AE080-485-0 3 x 480 Vac 3 x 80 A 5 % @ 480 Vac
LR3-AE100-483-0 3 x 480 Vac 3 x 100 A 3 % @ 480 Vac
LR3-AE100-485-0 3 x 480 Vac 3 x 100 A 5 % @ 480 Vac
LR3-AE125-483-0 3 x 480 Vac 3 x 125 A 3 % @ 480 Vac
LR3-AE125-485-0 3 x 480 Vac 3 x 125 A 5 % @ 480 Vac
LR3-AE160-483-0 3 x 480 Vac 3 x 160 A 3 % @ 480 Vac
LR3-AE160-485-0 3 x 480 Vac 3 x 160 A 5 % @ 480 Vac
LR3-AE200-483-0 3 x 480 Vac 3 x 200 A 3 % @ 480 Vac
LR3-AE200-485-0 3 x 480 Vac 3 x 200 A 5 % @ 480 Vac
LR3-AE250-483-0 3 x 480 Vac 3 x 250 A 3 % @ 480 Vac
LR3-AE250-485-0 3 x 480 Vac 3 x 250 A 5 % @ 480 Vac
LR3-AE315-483-0 3 x 480 Vac 3 x 315 A 3 % @ 480 Vac
LR3-AE315-485-0 3 x 480 Vac 3 x 315 A 5 % @ 480 Vac
LR3-AE400-483-0 3 x 480 Vac 3 x 400 A 3 % @ 480 Vac
LR3-AE400-485-0 3 x 480 Vac 3 x 400 A 5 % @ 480 Vac
LR3-AE500-483-0 3 x 480 Vac 3 x 500 A 3 % @ 480 Vac
LR3-AE500-485-0 3 x 480 Vac 3 x 500 A 5 % @ 480 Vac
LR3-AE630-483-0 3 x 480 Vac 3 x 630 A 3 % @ 480 Vac
LR3-AE630-485-0 3 x 480 Vac 3 x 630 A 5 % @ 480 Vac
LR3-AE710-483-0 3 x 480 Vac 3 x 710 A 3 % @ 480 Vac
LR3-AE710-485-0 3 x 480 Vac 3 x 710 A 5 % @ 480 Vac
LR3-AE900-483-0 3 x 480 Vac 3 x 900 A 3 % @ 480 Vac
LR3-AE900-485-0 3 x 480 Vac 3 x 900 A 5 % @ 480 Vac
Image of BLOCK Item: LR3-AE250-485-0
Technical files Data sheet Approvals / Manufacturer's declaration COA UL 508 & CSA 22.2 COC UL 508 & CSA 22.2 EU-Declaration of Conformity CAD/CAE data 3D-CAD-Model (STEP) Additional information Accessories touch protection

Technical Data for LR3-AE250-485-0

Operating data
Rated voltage 3 x 480 Vac
Rated voltage (IEC) 3 x 690 Vac
Rated voltage (UL) 3 x 600 Vac
Short circuit voltage uK 5 % @ 480 Vac
Voltage drop 11.5 Vac
Rated current 3 x 250 A
Rated frequency 50 - 60 Hz
Inductance 0.147 mH
Inductance deviation ±10%
Approvals
Approvals cULus
Environment
Ambient temperature +104 °F
Type of cooling AN
Safety and protection
Type Open type
Insulation class H
Protection index IP 00
Safety class I
Test voltage 2500 Vac
Terminal and mounting
Terminals phase Bolt, M8
Connection type Bolt, M10
Fixing method Fixing rail
Fixing screws M10
Measures and weights
Width 18.90 inch
Height 7.91 inch
Depth 9.67 inch
Weight 94.80 lbs

Information for LR3-A series

General Data
  • Rated current 3 x 4 - 3 x 900 A
  • Insulation class H
  • Inductance7,350 – 0,024 mH
  • Short-circuit voltage (uK) 3 %, 4 %, 5%
  • Rated voltage 3 x 400 Vac, 3 x 480 Vac
  • Degree of protection IP 00
  • Ambient temperature +104 °F / +40 °C
Benefits
  • Ensuring the short-circuit voltage of 3, 4 or 5 % to the mains
  • Increases the service life of equipment
  • Low ripple
  • Starting current limitation
  • Power harmonic mitigation
  • Use as line reactor, commutating reactor or PFC reactor
  • Bridging voltage dips
  • Peak current limitation
  • Very good corrosion protection and low noise due to vacuum impregnation
  • AD types with UL approval, AE types with UL Listed approval

Our recommendations for you

BLOCK product: COV 480x200x108
COV 480x200x108
Cover set COV for LR3-AE