HLD 110-500/250
Radio interference suppression filter HLD 110
Rated voltage
max. 3 x 520 Vac
Rated current
3 x 250 A
Leakage current (50 Hz)*
37 mA
Version | Rated voltage | Rated current | Leakage current (50 Hz)* | |
---|---|---|---|---|
HLD 110-500/8 | max. 3 x 520 Vac | 3 x 8 A | 20 mA | |
HLD 110-500/12 | max. 3 x 520 Vac | 3 x 12 A | 20 mA | |
HLD 110-500/16 | max. 3 x 520 Vac | 3 x 16 A | 21 mA | |
HLD 110-500/30 | max. 3 x 520 Vac | 3 x 30 A | 29 mA | |
HLD 110-500/42 | max. 3 x 520 Vac | 3 x 42 A | 20 mA | |
HLD 110-500/55 | max. 3 x 520 Vac | 3 x 55 A | 30 mA | |
HLD 110-500/75 | max. 3 x 520 Vac | 3 x 75 A | 22 mA | |
HLD 110-500/100 | max. 3 x 520 Vac | 3 x 100 A | 30 mA | |
HLD 110-500/130 | max. 3 x 520 Vac | 3 x 130 A | 22 mA | |
HLD 110-500/180 | max. 3 x 520 Vac | 3 x 180 A | 31 mA | |
HLD 110-500/250 | max. 3 x 520 Vac | 3 x 250 A | 37 mA |
DOWNLOADS
Technical files
Data sheet
Approvals / Manufacturer's declaration
Manufacturer's declaration to EN 60939-2
COA UL 1283 & CSA 22.2
COC UL 1283 & CSA 22.2
CAD/CAE data
3D-CAD-Model (STEP)
ePlan Makro
Technical Data for HLD 110-500/250
Operating data | |
---|---|
Rated voltage | max. 3 x 520 Vac |
Voltage range | 3 x 0 - 520 Vac |
Rated current | 3 x 250 A |
Leakage current (50 Hz)* | 37 mA |
Leakage current (50 Hz)** | 355 mA |
Rated frequency | 50 - 60 Hz |
Power loss | 180 W |
Overrating Capacity | 150 %, shortly |
Approvals | |
---|---|
Approvals | cURus, UL 1283 5th edition, CSA 22.2 No.8 |
Environment | |
---|---|
Ambient temperature max. | 122.0 °F |
Climatic category | 25/085/21 [in accordance with EN 60068-1] |
Safety and protection | |
---|---|
SCCR*** | 100 kA |
Protection index | IP 20 |
Type | Metal enclosure |
Safety class (prepared) | I |
Test voltage | 2150 Vdc Phase/Phase, 2700 Vdc Phase/PE |
Terminal and mounting | |
---|---|
Terminals phase | Screw clamp, 150 mm² |
Connection type | Bolt, M12 |
Fixing method | Mounting lugs |
Fixing screws | M6 |
Measures and weights | |
---|---|
Depth | 20.67 inch |
Height | 8.66 inch |
Width | 6.10 inch |
Weight | 26.90 lbs |
Notes | |
---|---|
* | Leakage current measured against the maximum permissible input voltage fluctuation in accordance with IEC 38 ±10 % |
** | Leakage current by loss of two phases |
*** | with corresponding preliminary fuse |
Information for HLD 110 series
General Data
- Rated voltage 3 x 520 Vac
- Ambient temperature max. 122 °F / 50 °C
- Leakage current 20.00 to 37.00 mA
- Rated current 3 x 8 - 3 x 250 A
- Voltage range 3 x 0 - 520 Vac
- Degree of protection IP 20
Benefits
- Single-stage filter concept
- For enhanced EMI suppression
- Increase in the interference immunity of the connected equipment
- Efficient filter effect against line-bound interference emissions