HFD 156-400/10

Radio interference suppression filter HFD 156

Version HFD 156-400/10
Rated voltage max. 3 x 480 Vac Rated current 3 x 10 A Leakage current (50 Hz)* 1 mA
Version Rated voltage Rated current Leakage current (50 Hz)*
HFD 156-400/3 max. 3 x 480 Vac 3 x 3 A 1 mA
HFD 156-400/6 max. 3 x 480 Vac 3 x 6 A 1 mA
HFD 156-400/10 max. 3 x 480 Vac 3 x 10 A 1 mA
HFD 156-400/12 max. 3 x 480 Vac 3 x 12 A 1 mA
HFD 156-400/16 max. 3 x 480 Vac 3 x 16 A 1 mA
Image of BLOCK Item: HFD 156-400/10
Technical files Data sheet Approvals / Manufacturer's declaration Manufacturer's declaration to EN 60939-2 CAD/CAE data 3D-CAD-Model (STEP)

Technical Data for HFD 156-400/10

Operating data
Rated voltage max. 3 x 480 Vac
Voltage range 3 x 0 - 480 Vac
Rated current 3 x 10 A
Leakage current (50 Hz)** 9 mA
Leakage current (50 Hz)* 1 mA
Rated frequency 50 - 60 Hz
Power loss 4.7 W
Overrating Capacity 150 %, shortly
Environment
Ambient temperature max. 113.0 °F
Climatic category 25/085/21
[in accordance with EN 60068-1]
Safety and protection
Type Metal enclosure
Protection index IP 20
Safety class (prepared) I
Test voltage 2100 Vdc Phase/Phase, 2700 Vdc Phase/PE
Terminal and mounting
Terminals phase 2.5 mm² spring terminal
Connection type Tab connector, 6.3 x 0.8 mm
Fixing method DIN Rail mounting
Measures and weights
Depth 5.00 inch
Height 4.33 inch
Width 1.77 inch
Weight 1.08 lbs
Notes
* Leakage current measured against the maximum permissible input voltage fluctuation in accordance with IEC 38 ±10 %
** Leakage current by loss of two phases

Information for HFD 156 series

General Data
  • Rated current 3 x 3 - 3 x 16 A
  • Degree of protection IP 20
  • Rated voltage 3 x 480 Vac
  • Voltage range 3 x 0 - 480 Vac
  • Leakage current 1.00 mA
  • Ambient temperature max. 113 °F / 45 °C
Benefits
  • Increase in the interference immunity of the connected equipment
  • Efficient filter effect against line-bound interference emissions
  • Single-stage filter concept
  • DIN rail mounting
  • For general EMI suppression

Our recommendations for you

BLOCK product: LR3 40-4/10
LR3 40-4/10
Line reactor, three-phase
3 x 400 Vac, 3 x 2 – 3 x 1600 A, 0.019 – 18.500 mH, Use as line reactor, commutating reactor or PFC reactor
View accessory
BLOCK product: HF1K 7-400
HF1K 7-400
Harmonic filter
3 x 400 Vac, 3 x 10 – 3 x 144 A , 5.5 – 90 kW, Power factor >0,95 at rated current
View accessory
BLOCK product: LR3-AD010-404-0
LR3-AD010-404-0
Line reactor, three-phase
3 x 400 Vac, 3 x 4 - 3 x 900 A, 7,350 – 0,024 mH, Use as line reactor, commutating reactor or PFC reactor
View accessory