EB-1824-010-0
1-Channel circuit breaker communicative EasyB
Input rated voltage
24 Vdc
Output rated current
1 A
Version | Input rated voltage | Output rated current | ||
---|---|---|---|---|
EB-0824-100-0 | 24 Vdc | 0.5 - 10 A, adjustable (0,5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A) | ||
EB-0824-100-4 | 24 Vdc | 0.5 - 10 A, adjustable (0,5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A) | ||
EB-1824-010-0 | 24 Vdc | 1 A | ||
EB-1824-020-0 | 24 Vdc | 2 A | ||
EB-1824-030-0 | 24 Vdc | 3 A | ||
EB-1824-040-0 | 24 Vdc | 4 A | ||
EB-1824-060-0 | 24 Vdc | 6 A | ||
EB-1824-080-0 | 24 Vdc | 8 A | ||
EB-1824-100-0 | 24 Vdc | 10 A | ||
EB-3824-100-0 | 24 Vdc | 0,5 - 10 A, adjustable (0,5A, 1A, 2A, 3A, 4A, 5A, 6A, 8A, 10A) |
DOWNLOADS
Technical files
Manual
Dimension sheet
Instruction manual
Approvals / Manufacturer's declaration
UL 508 Listed USA (E219022)
UL 508 Listed Canada (E219022)
COC UL 508 & CSA 22.2
UL 2367 USA (E356250)
COA UL 2367 & CSA 22.2
COC UL 2367 & CSA 22.2
Marine DNV GL (TAA000022T)
EAC approval
EU-Declaration of Conformity
CAD/CAE data
ePlan Macro
3D-CAD-Model (STEP)
Additional information
Brochure EasyB
eBreaker brochure
Technical Data for EB-1824-010-0
Input | |
---|---|
Input rated voltage | 24 Vdc |
Input voltage range | 18 - 30 Vdc |
Maximal residual ripple of supplied input voltage | 3 % |
Max. total input current | 1 A |
Max. input current for each pole of terminal | 10 A (-), 40 A (+) |
Required input voltage for turning-on of outputs | 17.5 Vdc (Turn-off Threshold 16.7 Vdc), ± 0.7 Vdc |
Max. power losses | 1,2 W |
Over voltage protection | Suppressor diode 33 Vdc |
Stand-by current | 39 mA @ 24 Vdc |
Power losses in stand-by mode | 1,17 W @ 24 Vdc |
Turn on capacity | 110 mF @ 24 Vdc / 2,5 mm² / 2,5 m |
Output | |
---|---|
Output rated voltage | 24 Vdc |
Maximum voltage drop between input and output | 58 mV |
Initialization time of module | 52 ms |
Turn-on delay of outputs | min. 50 ms / max. 5 s |
Waiting periode after switch-off of an output | 500 ms (Short circuit) … 5 s (Overload) |
Maximum turn-on capacity for each channel | 100 mF |
Parallel use of outputs | Not allowed |
Serial use of outputs | Not allowed |
Resistance to reverse feed max. | 35 Vdc |
Output rated current | 1 A |
Efficiency | 99 % |
Output limited current | typ. 1,25 A |
Signaling | |
---|---|
Bus communication | Read:-state (tripped, On, Off) -set/active current -input voltage -firmware version/serial number Write:-state (on, off, reset) |
Status indicator | LED (red, green, orange) |
Signal output | Output status, short circuit proof high = Channel on, low = Channel off, fault |
Signal output (ON/OFF/Reset) | Reset input Level high = min. 15 Vdc, max. 30 Vdc Level low = min. 0 Vdc, max. 5 Vdc |
Approvals | |
---|---|
Approvals | cURus, cULus, DNV GL |
Environment | |
---|---|
Type of cooling | Natural convection |
Ambient temperature | -25 °C to +70 °C |
Storage temperature | -13 °F … +185 °F |
Derating | - |
Relative humidity | 5 … 96 %, without condensation |
Required minimum spacing (left/right) | 0.00 inch |
Required minimum spacing (over/under) | 1.18 inch |
Safety and protection | |
---|---|
Protection index | IP 20 |
Safety class | III, without PE connection |
Degree of pollution | 2 |
Terminal and mounting | |
---|---|
Terminals input, (spring clamp terminal) | max. 16 mm² |
Terminals output, (spring clamp terminal) | max 2,5 mm² (1 x "+") |
Terminals signalling, (spring clamp terminal) | max. 2,5 mm² |
Mounting position | horizontal for standard rail DIN TS35 |
Measures and weights | |
---|---|
Width | 0.47 inch |
Height | 3.90 inch |
Depth | 2.36 inch |
Weight | 0.09 lbs |
Information for EasyB 1-Channel current-limiting, communicative series
General Data
- Up to 40 fuse channels stackable side by side
- Ambient temperature -13 °F / -25 °C to +158 °F / 70 °C
- Common signaling output for tripped and switched off channels
- Active current limiting
- Protection index IP 20
- Multi-coloured LED and status display button
- Efficiency 99 %
- 24 Vdc 1-channel circuit breaker system
Benefits
- Optional undervoltage shutdown in combined network
- Additional load outputs through output expanders mountable sidewise
- Automatic channel assignment
- Communication via communication modules
- Optional settings for tripping current
- Selective load-dependent activation
- Common reset input
- 3 years warranty