Line reactors reduce low frequency interference (harmonics) and relieve the strain on the supply network through compensation of the distortion reactive power induced by this. The connected consumers are spared by limiting the starting current, thereby increasing their lifetime. The BLOCK standard product range includes series with 3%, 4% and 5% short circuit voltage.
Overview:
◼︎ Reduction in current harmonics (THDi)
◼︎ Protection of the grid against power line disturbances
◼︎ Compliance with the harmonics limit values required under standards
◼︎ Reduction in reactive power consumption
◼︎ Reduction in losses at the line transformer and in neutral wire load
◼︎ Increased immunity for your system from interference
Product search for Line reactors
Phases
Connections
Fixing method
Rated Voltage
Rated Current
- 10 A (2)
- 100 A (2)
- 125 A (1)
- 16 A (2)
- 2 A (2)
- 2.5 A (1)
- 20 A (2)
- 25 A (2)
- 3 x 10 A (6)
- 3 x 100 A (8)
- 3 x 1000 A (5)
- 3 x 115 A (5)
- 3 x 1200 A (5)
- 3 x 125 A (8)
- 3 x 1400 A (5)
- 3 x 16 A (6)
- 3 x 160 A (8)
- 3 x 1600 A (5)
- 3 x 180 A (5)
- 3 x 2 A (5)
- 3 x 20 A (6)
- 3 x 200 A (8)
- 3 x 25 A (6)
- 3 x 250 A (8)
- 3 x 30 A (6)
- 3 x 300 A (5)
- 3 x 315 A (3)
- 3 x 35 A (6)
- 3 x 4 A (6)
- 3 x 40 A (6)
- 3 x 400 A (8)
- 3 x 45 A (6)
- 3 x 50 A (6)
- 3 x 500 A (8)
- 3 x 6 A (6)
- 3 x 63 A (9)
- 3 x 630 A (8)
- 3 x 70 A (5)
- 3 x 710 A (8)
- 3 x 8 A (6)
- 3 x 80 A (9)
- 3 x 800 A (5)
- 3 x 90 A (5)
- 3 x 900 A (3)
- 35 A (2)
- 4 A (2)
- 40 A (2)
- 50 A (2)
- 6 A (2)
- 63 A (2)
254 Versions of 5 products
Or do you have different requirements?
We can help you!
LR3-A
Line reactor, three-phase
3 x 400 Vac, 3 x 4 - 3 x 900 A, 7,350 – 0,024 mH, Use as line reactor, commutating reactor or PFC reactor
Version | Rated voltage | Rated current | Short circuit voltage uK | |
---|---|---|---|---|
LR3-AD004-404-0 | 3 x 400 Vac | 3 x 4 A | 4 % @ 400 Vac | |
LR3-AD006-404-0 | 3 x 400 Vac | 3 x 6 A | 4 % @ 400 Vac | |
LR3-AD008-404-0 | 3 x 400 Vac | 3 x 8 A | 4 % @ 400 Vac | |
LR3-AD010-404-0 | 3 x 400 Vac | 3 x 10 A | 4 % @ 400 Vac | |
LR3-AD016-404-0 | 3 x 400 Vac | 3 x 16 A | 4 % @ 400 Vac | |
LR3-AD020-404-0 | 3 x 400 Vac | 3 x 20 A | 4 % @ 400 Vac | |
LR3-AD025-404-0 | 3 x 400 Vac | 3 x 25 A | 4 % @ 400 Vac | |
LR3-AD030-404-0 | 3 x 400 Vac | 3 x 30 A | 4 % @ 400 Vac | |
LR3-AD035-404-0 | 3 x 400 Vac | 3 x 35 A | 4 % @ 400 Vac | |
LR3-AD040-404-0 | 3 x 400 Vac | 3 x 40 A | 4 % @ 400 Vac | |
LR3-AD045-404-0 | 3 x 400 Vac | 3 x 45 A | 4 % @ 400 Vac | |
LR3-AD050-404-0 | 3 x 400 Vac | 3 x 50 A | 4 % @ 400 Vac | |
LR3-AD063-404-0 | 3 x 400 Vac | 3 x 63 A | 4 % @ 400 Vac | |
LR3-AE063-404-0 | 3 x 400 Vac | 3 x 63 A | 4 % @ 400 Vac | |
LR3-AD080-404-0 | 3 x 400 Vac | 3 x 80 A | 4 % @ 400 Vac | |
LR3-AE080-404-0 | 3 x 400 Vac | 3 x 80 A | 4 % @ 400 Vac | |
LR3-AE100-404-0 | 3 x 400 Vac | 3 x 100 A | 4 % @ 400 Vac | |
LR3-AE125-404-0 | 3 x 400 Vac | 3 x 125 A | 4 % @ 400 Vac | |
LR3-AE160-404-0 | 3 x 400 Vac | 3 x 160 A | 4 % @ 400 Vac | |
LR3-AE200-404-0 | 3 x 400 Vac | 3 x 200 A | 4 % @ 400 Vac | |
LR3-AE250-404-0 | 3 x 400 Vac | 3 x 250 A | 4 % @ 400 Vac | |
LR3-AE315-404-0 | 3 x 400 Vac | 3 x 315 A | 4 % @ 400 Vac | |
LR3-AE400-404-0 | 3 x 400 Vac | 3 x 400 A | 4 % @ 400 Vac | |
LR3-AE500-404-0 | 3 x 400 Vac | 3 x 500 A | 4 % @ 400 Vac | |
LR3-AE630-404-0 | 3 x 400 Vac | 3 x 630 A | 4 % @ 400 Vac | |
LR3-AE710-404-0 | 3 x 400 Vac | 3 x 710 A | 4 % @ 400 Vac | |
LR3-AE900-404-0 | 3 x 400 Vac | 3 x 900 A | 4 % @ 400 Vac | |
LR3-AE063-483-0 | 3 x 480 Vac | 3 x 63 A | 3 % @ 480 Vac | |
LR3-AE063-485-0 | 3 x 480 Vac | 3 x 63 A | 5 % @ 480 Vac | |
LR3-AE080-483-0 | 3 x 480 Vac | 3 x 80 A | 3 % @ 480 Vac | |
LR3-AE080-485-0 | 3 x 480 Vac | 3 x 80 A | 5 % @ 480 Vac | |
LR3-AE100-483-0 | 3 x 480 Vac | 3 x 100 A | 3 % @ 480 Vac | |
LR3-AE100-485-0 | 3 x 480 Vac | 3 x 100 A | 5 % @ 480 Vac | |
LR3-AE125-483-0 | 3 x 480 Vac | 3 x 125 A | 3 % @ 480 Vac | |
LR3-AE125-485-0 | 3 x 480 Vac | 3 x 125 A | 5 % @ 480 Vac | |
LR3-AE160-483-0 | 3 x 480 Vac | 3 x 160 A | 3 % @ 480 Vac | |
LR3-AE160-485-0 | 3 x 480 Vac | 3 x 160 A | 5 % @ 480 Vac | |
LR3-AE200-483-0 | 3 x 480 Vac | 3 x 200 A | 3 % @ 480 Vac | |
LR3-AE200-485-0 | 3 x 480 Vac | 3 x 200 A | 5 % @ 480 Vac | |
LR3-AE250-483-0 | 3 x 480 Vac | 3 x 250 A | 3 % @ 480 Vac | |
LR3-AE250-485-0 | 3 x 480 Vac | 3 x 250 A | 5 % @ 480 Vac | |
LR3-AE315-483-0 | 3 x 480 Vac | 3 x 315 A | 3 % @ 480 Vac | |
LR3-AE315-485-0 | 3 x 480 Vac | 3 x 315 A | 5 % @ 480 Vac | |
LR3-AE400-483-0 | 3 x 480 Vac | 3 x 400 A | 3 % @ 480 Vac | |
LR3-AE400-485-0 | 3 x 480 Vac | 3 x 400 A | 5 % @ 480 Vac | |
LR3-AE500-483-0 | 3 x 480 Vac | 3 x 500 A | 3 % @ 480 Vac | |
LR3-AE500-485-0 | 3 x 480 Vac | 3 x 500 A | 5 % @ 480 Vac | |
LR3-AE630-483-0 | 3 x 480 Vac | 3 x 630 A | 3 % @ 480 Vac | |
LR3-AE630-485-0 | 3 x 480 Vac | 3 x 630 A | 5 % @ 480 Vac | |
LR3-AE710-483-0 | 3 x 480 Vac | 3 x 710 A | 3 % @ 480 Vac | |
LR3-AE710-485-0 | 3 x 480 Vac | 3 x 710 A | 5 % @ 480 Vac | |
LR3-AE900-483-0 | 3 x 480 Vac | 3 x 900 A | 3 % @ 480 Vac | |
LR3-AE900-485-0 | 3 x 480 Vac | 3 x 900 A | 5 % @ 480 Vac |
Or do you have different requirements?
We can help you!
LR3 400
Line reactor, three-phase
3 x 400 Vac, 3 x 2 – 3 x 1600 A, 0.019 – 18.500 mH, Use as line reactor, commutating reactor or PFC reactor
Version | Rated voltage | Rated current | Short circuit voltage uK | |
---|---|---|---|---|
LR3 40-3/2 | 3 x 400 Vac | 3 x 2 A | 3 % @ 400 Vac | |
LR3 40-4/2 | 3 x 400 Vac | 3 x 2 A | 4 % @ 400 Vac | |
LR3 40-5/2 | 3 x 400 Vac | 3 x 2 A | 5 % @ 400 Vac | |
LR3 40-3/4 | 3 x 400 Vac | 3 x 4 A | 3 % @ 400 Vac | |
LR3 40-4/4 | 3 x 400 Vac | 3 x 4 A | 4 % @ 400 Vac | |
LR3 40-5/4 | 3 x 400 Vac | 3 x 4 A | 5 % @ 400 Vac | |
LR3 40-3/6 | 3 x 400 Vac | 3 x 6 A | 3 % @ 400 Vac | |
LR3 40-4/6 | 3 x 400 Vac | 3 x 6 A | 4 % @ 400 Vac | |
LR3 40-5/6 | 3 x 400 Vac | 3 x 6 A | 5 % @ 400 Vac | |
LR3 40-3/8 | 3 x 400 Vac | 3 x 8 A | 3 % @ 400 Vac | |
LR3 40-4/8 | 3 x 400 Vac | 3 x 8 A | 4 % @ 400 Vac | |
LR3 40-5/8 | 3 x 400 Vac | 3 x 8 A | 5 % @ 400 Vac | |
LR3 40-3/10 | 3 x 400 Vac | 3 x 10 A | 3 % @ 400 Vac | |
LR3 40-4/10 | 3 x 400 Vac | 3 x 10 A | 4 % @ 400 Vac | |
LR3 40-5/10 | 3 x 400 Vac | 3 x 10 A | 5 % @ 400 Vac | |
LR3 40-3/16 | 3 x 400 Vac | 3 x 16 A | 3 % @ 400 Vac | |
LR3 40-4/16 | 3 x 400 Vac | 3 x 16 A | 4 % @ 400 Vac | |
LR3 40-5/16 | 3 x 400 Vac | 3 x 16 A | 5 % @ 400 Vac | |
LR3 40-3/20 | 3 x 400 Vac | 3 x 20 A | 3 % @ 400 Vac | |
LR3 40-4/20 | 3 x 400 Vac | 3 x 20 A | 4 % @ 400 Vac | |
LR3 40-5/20 | 3 x 400 Vac | 3 x 20 A | 5 % @ 400 Vac | |
LR3 40-3/25 | 3 x 400 Vac | 3 x 25 A | 3 % @ 400 Vac | |
LR3 40-4/25 | 3 x 400 Vac | 3 x 25 A | 4 % @ 400 Vac | |
LR3 40-5/25 | 3 x 400 Vac | 3 x 25 A | 5 % @ 400 Vac | |
LR3 40-3/30 | 3 x 400 Vac | 3 x 30 A | 3 % @ 400 Vac | |
LR3 40-4/30 | 3 x 400 Vac | 3 x 30 A | 4 % @ 400 Vac | |
LR3 40-5/30 | 3 x 400 Vac | 3 x 30 A | 5 % @ 400 Vac | |
LR3 40-3/35 | 3 x 400 Vac | 3 x 35 A | 3 % @ 400 Vac | |
LR3 40-4/35 | 3 x 400 Vac | 3 x 35 A | 4 % @ 400 Vac | |
LR3 40-5/35 | 3 x 400 Vac | 3 x 35 A | 5 % @ 400 Vac | |
LR3 40-3/40 | 3 x 400 Vac | 3 x 40 A | 3 % @ 400 Vac | |
LR3 40-4/40 | 3 x 400 Vac | 3 x 40 A | 4 % @ 400 Vac | |
LR3 40-5/40 | 3 x 400 Vac | 3 x 40 A | 5 % @ 400 Vac | |
LR3 40-3/45 | 3 x 400 Vac | 3 x 45 A | 3 % @ 400 Vac | |
LR3 40-4/45 | 3 x 400 Vac | 3 x 45 A | 4 % @ 400 Vac | |
LR3 40-5/45 | 3 x 400 Vac | 3 x 45 A | 5 % @ 400 Vac | |
LR3 40-3/50 | 3 x 400 Vac | 3 x 50 A | 3 % @ 400 Vac | |
LR3 40-4/50 | 3 x 400 Vac | 3 x 50 A | 4 % @ 400 Vac | |
LR3 40-5/50 | 3 x 400 Vac | 3 x 50 A | 5 % @ 400 Vac | |
LR3 40-3/63 | 3 x 400 Vac | 3 x 63 A | 3 % @ 400 Vac | |
LR3 40-4/63 | 3 x 400 Vac | 3 x 63 A | 4 % @ 400 Vac | |
LR3 40-5/63 | 3 x 400 Vac | 3 x 63 A | 5 % @ 400 Vac | |
LR3 40-3/70 | 3 x 400 Vac | 3 x 70 A | 3 % @ 400 Vac | |
LR3 40-4/70 | 3 x 400 Vac | 3 x 70 A | 4 % @ 400 Vac | |
LR3 40-5/70 | 3 x 400 Vac | 3 x 70 A | 5 % @ 400 Vac | |
LR3 40-3/80 | 3 x 400 Vac | 3 x 80 A | 3 % @ 400 Vac | |
LR3 40-4/80 | 3 x 400 Vac | 3 x 80 A | 4 % @ 400 Vac | |
LR3 40-5/80 | 3 x 400 Vac | 3 x 80 A | 5 % @ 400 Vac | |
LR3 40-3/90 | 3 x 400 Vac | 3 x 90 A | 3 % @ 400 Vac | |
LR3 40-4/90 | 3 x 400 Vac | 3 x 90 A | 4 % @ 400 Vac | |
LR3 40-5/90 | 3 x 400 Vac | 3 x 90 A | 5 % @ 400 Vac | |
LR3 40-3/100 | 3 x 400 Vac | 3 x 100 A | 3 % @ 400 Vac | |
LR3 40-4/100 | 3 x 400 Vac | 3 x 100 A | 4 % @ 400 Vac | |
LR3 40-5/100 | 3 x 400 Vac | 3 x 100 A | 5 % @ 400 Vac | |
LR3 40-3/115 | 3 x 400 Vac | 3 x 115 A | 3 % @ 400 Vac | |
LR3 40-4/115 | 3 x 400 Vac | 3 x 115 A | 4 % @ 400 Vac | |
LR3 40-5/115 | 3 x 400 Vac | 3 x 115 A | 5 % @ 400 Vac | |
LR3 40-3/125 | 3 x 400 Vac | 3 x 125 A | 3 % @ 400 Vac | |
LR3 40-4/125 | 3 x 400 Vac | 3 x 125 A | 4 % @ 400 Vac | |
LR3 40-5/125 | 3 x 400 Vac | 3 x 125 A | 5 % @ 400 Vac | |
LR3 40-3/160 | 3 x 400 Vac | 3 x 160 A | 3 % @ 400 Vac | |
LR3 40-4/160 | 3 x 400 Vac | 3 x 160 A | 4 % @ 400 Vac | |
LR3 40-5/160 | 3 x 400 Vac | 3 x 160 A | 5 % @ 400 Vac | |
LR3 40-3/180 | 3 x 400 Vac | 3 x 180 A | 3 % @ 400 Vac | |
LR3 40-4/180 | 3 x 400 Vac | 3 x 180 A | 4 % @ 400 Vac | |
LR3 40-5/180 | 3 x 400 Vac | 3 x 180 A | 5 % @ 400 Vac | |
LR3 40-3/200 | 3 x 400 Vac | 3 x 200 A | 3 % @ 400 Vac | |
LR3 40-4/200 | 3 x 400 Vac | 3 x 200 A | 4 % @ 400 Vac | |
LR3 40-5/200 | 3 x 400 Vac | 3 x 200 A | 5 % @ 400 Vac | |
LR3 40-3/250 | 3 x 400 Vac | 3 x 250 A | 3 % @ 400 Vac | |
LR3 40-4/250 | 3 x 400 Vac | 3 x 250 A | 4 % @ 400 Vac | |
LR3 40-5/250 | 3 x 400 Vac | 3 x 250 A | 5 % @ 400 Vac | |
LR3 40-3/300 | 3 x 400 Vac | 3 x 300 A | 3 % @ 400 Vac | |
LR3 40-4/300 | 3 x 400 Vac | 3 x 300 A | 4 % @ 400 Vac | |
LR3 40-5/300 | 3 x 400 Vac | 3 x 300 A | 5 % @ 400 Vac | |
LR3 40-3/400 | 3 x 400 Vac | 3 x 400 A | 3 % @ 400 Vac | |
LR3 40-4/400 | 3 x 400 Vac | 3 x 400 A | 4 % @ 400 Vac | |
LR3 40-5/400 | 3 x 400 Vac | 3 x 400 A | 5 % @ 400 Vac | |
LR3 40-3/500 | 3 x 400 Vac | 3 x 500 A | 3 % @ 400 Vac | |
LR3 40-4/500 | 3 x 400 Vac | 3 x 500 A | 4 % @ 400 Vac | |
LR3 40-5/500 | 3 x 400 Vac | 3 x 500 A | 5 % @ 400 Vac | |
LR3 40-3/630 | 3 x 400 Vac | 3 x 630 A | 3 % @ 400 Vac | |
LR3 40-4/630 | 3 x 400 Vac | 3 x 630 A | 4 % @ 400 Vac | |
LR3 40-5/630 | 3 x 400 Vac | 3 x 630 A | 5 % @ 400 Vac | |
LR3 40-3/710 | 3 x 400 Vac | 3 x 710 A | 3 % @ 400 Vac | |
LR3 40-4/710 | 3 x 400 Vac | 3 x 710 A | 4 % @ 400 Vac | |
LR3 40-5/710 | 3 x 400 Vac | 3 x 710 A | 5 % @ 400 Vac | |
LR3 40-3/800 | 3 x 400 Vac | 3 x 800 A | 3 % @ 400 Vac | |
LR3 40-4/800 | 3 x 400 Vac | 3 x 800 A | 4 % @ 400 Vac | |
LR3 40-5/800 | 3 x 400 Vac | 3 x 800 A | 5 % @ 400 Vac | |
LR3 40-3/1000 | 3 x 400 Vac | 3 x 1000 A | 3 % @ 400 Vac | |
LR3 40-4/1000 | 3 x 400 Vac | 3 x 1000 A | 4 % @ 400 Vac | |
LR3 40-5/1000 | 3 x 400 Vac | 3 x 1000 A | 5 % @ 400 Vac | |
LR3 40-3/1200 | 3 x 400 Vac | 3 x 1200 A | 3 % @ 400 Vac | |
LR3 40-4/1200 | 3 x 400 Vac | 3 x 1200 A | 4 % @ 400 Vac | |
LR3 40-5/1200 | 3 x 400 Vac | 3 x 1200 A | 5 % @ 400 Vac | |
LR3 40-3/1400 | 3 x 400 Vac | 3 x 1400 A | 3 % @ 400 Vac | |
LR3 40-4/1400 | 3 x 400 Vac | 3 x 1400 A | 4 % @ 400 Vac | |
LR3 40-5/1400 | 3 x 400 Vac | 3 x 1400 A | 5 % @ 400 Vac | |
LR3 40-3/1600 | 3 x 400 Vac | 3 x 1600 A | 3 % @ 400 Vac | |
LR3 40-4/1600 | 3 x 400 Vac | 3 x 1600 A | 4 % @ 400 Vac | |
LR3 40-5/1600 | 3 x 400 Vac | 3 x 1600 A | 5 % @ 400 Vac |
Or do you have different requirements?
We can help you!
LR3 480
Line reactor, three-phase
3 x 480 Vac, 3 x 2 – 3 x 1600 A, 0.014 - 18.500 mH, Use as line reactor, commutating reactor or PFC reactor
Version | Rated voltage | Rated current | Short circuit voltage uK | |
---|---|---|---|---|
LR3 48-3/2 | max. 3 x 480 Vac | 2 A | 3 % @ 480 Vac | |
LR3 48-5/2 | max. 3 x 480 Vac | 2 A | 5 % @ 480 Vac | |
LR3 48-3/4 | max. 3 x 480 Vac | 4 A | 3 % @ 480 Vac | |
LR3 48-5/4 | max. 3 x 480 Vac | 4 A | 5 % @ 480 Vac | |
LR3 48-3/6 | max. 3 x 480 Vac | 6 A | 3 % @ 480 Vac | |
LR3 48-5/6 | max. 3 x 480 Vac | 6 A | 5 % @ 480 Vac | |
LR3 48-3/8 | max. 3 x 480 Vac | 8 A | 3 % @ 480 Vac | |
LR3 48-5/8 | max. 3 x 480 Vac | 8 A | 5 % @ 480 Vac | |
LR3 48-3/10 | max. 3 x 480 Vac | 10 A | 3 % @ 480 Vac | |
LR3 48-5/10 | max. 3 x 480 Vac | 10 A | 5 % @ 480 Vac | |
LR3 48-3/16 | max. 3 x 480 Vac | 16 A | 3 % @ 480 Vac | |
LR3 48-5/16 | max. 3 x 480 Vac | 16 A | 5 % @ 480 Vac | |
LR3 48-3/20 | max. 3 x 480 Vac | 20 A | 3 % @ 480 Vac | |
LR3 48-5/20 | max. 3 x 480 Vac | 20 A | 5 % @ 480 Vac | |
LR3 48-3/25 | max. 3 x 480 Vac | 25 A | 3 % @ 480 Vac | |
LR3 48-5/25 | max. 3 x 480 Vac | 25 A | 5 % @ 480 Vac | |
LR3 48-3/30 | max. 3 x 480 Vac | 30 A | 3 % @ 480 Vac | |
LR3 48-5/30 | max. 3 x 480 Vac | 30 A | 5 % @ 480 Vac | |
LR3 48-3/35 | max. 3 x 480 Vac | 35 A | 3 % @ 480 Vac | |
LR3 48-5/35 | max. 3 x 480 Vac | 35 A | 5 % @ 480 Vac | |
LR3 48-3/40 | max. 3 x 480 Vac | 40 A | 3 % @ 480 Vac | |
LR3 48-5/40 | max. 3 x 480 Vac | 40 A | 5 % @ 480 Vac | |
LR3 48-3/45 | max. 3 x 480 Vac | 45 A | 3 % @ 480 Vac | |
LR3 48-5/45 | max. 3 x 480 Vac | 45 A | 5 % @ 480 Vac | |
LR3 48-3/50 | max. 3 x 480 Vac | 50 A | 3 % @ 480 Vac | |
LR3 48-5/50 | max. 3 x 480 Vac | 50 A | 5 % @ 480 Vac | |
LR3 48-3/63 | max. 3 x 480 Vac | 63 A | 3 % @ 480 Vac | |
LR3 48-5/63 | max. 3 x 480 Vac | 63 A | 5 % @ 480 Vac | |
LR3 48-3/70 | max. 3 x 480 Vac | 70 A | 3 % @ 480 Vac | |
LR3 48-5/70 | max. 3 x 480 Vac | 70 A | 5 % @ 480 Vac | |
LR3 48-3/80 | max. 3 x 480 Vac | 80 A | 3 % @ 480 Vac | |
LR3 48-5/80 | max. 3 x 480 Vac | 80 A | 5 % @ 480 Vac | |
LR3 48-3/90 | max. 3 x 480 Vac | 90 A | 3 % @ 480 Vac | |
LR3 48-5/90 | max. 3 x 480 Vac | 90 A | 5 % @ 480 Vac | |
LR3 48-3/100 | max. 3 x 480 Vac | 100 A | 3 % @ 480 Vac | |
LR3 48-5/100 | max. 3 x 480 Vac | 100 A | 5 % @ 480 Vac | |
LR3 48-3/115 | max. 3 x 480 Vac | 115 A | 3 % @ 480 Vac | |
LR3 48-5/115 | max. 3 x 480 Vac | 115 A | 5 % @ 480 Vac | |
LR3 48-3/125 | max. 3 x 480 Vac | 125 A | 3 % @ 480 Vac | |
LR3 48-5/125 | max. 3 x 480 Vac | 125 A | 5 % @ 480 Vac | |
LR3 48-3/160 | max. 3 x 480 Vac | 160 A | 3 % @ 480 Vac | |
LR3 48-5/160 | max. 3 x 480 Vac | 160 A | 5 % @ 480 Vac | |
LR3 48-3/180 | max. 3 x 480 Vac | 180 A | 3 % @ 480 Vac | |
LR3 48-5/180 | max. 3 x 480 Vac | 180 A | 5 % @ 480 Vac | |
LR3 48-3/200 | max. 3 x 480 Vac | 200 A | 3 % @ 480 Vac | |
LR3 48-5/200 | max. 3 x 480 Vac | 200 A | 5 % @ 480 Vac | |
LR3 48-3/250 | max. 3 x 480 Vac | 250 A | 3 % @ 480 Vac | |
LR3 48-5/250 | max. 3 x 480 Vac | 250 A | 5 % @ 480 Vac | |
LR3 48-3/300 | max. 3 x 480 Vac | 300 A | 3 % @ 480 Vac | |
LR3 48-5/300 | max. 3 x 480 Vac | 300 A | 5 % @ 480 Vac | |
LR3 48-3/400 | max. 3 x 480 Vac | 400 A | 3 % @ 480 Vac | |
LR3 48-5/400 | max. 3 x 480 Vac | 400 A | 5 % @ 480 Vac | |
LR3 48-3/500 | max. 3 x 480 Vac | 500 A | 3 % @ 480 Vac | |
LR3 48-5/500 | max. 3 x 480 Vac | 500 A | 5 % @ 480 Vac | |
LR3 48-3/630 | max. 3 x 480 Vac | 630 A | 3 % @ 480 Vac | |
LR3 48-5/630 | max. 3 x 480 Vac | 630 A | 5 % @ 480 Vac | |
LR3 48-3/710 | max. 3 x 480 Vac | 710 A | 3 % @ 480 Vac | |
LR3 48-5/710 | max. 3 x 480 Vac | 710 A | 5 % @ 480 Vac | |
LR3 48-3/800 | max. 3 x 480 Vac | 800 A | 3 % @ 480 Vac | |
LR3 48-5/800 | max. 3 x 480 Vac | 800 A | 5 % @ 480 Vac | |
LR3 48-3/1000 | max. 3 x 480 Vac | 1000 A | 3 % @ 480 Vac | |
LR3 48-5/1000 | max. 3 x 480 Vac | 1000 A | 5 % @ 480 Vac | |
LR3 48-3/1200 | max. 3 x 480 Vac | 1200 A | 3 % @ 480 Vac | |
LR3 48-5/1200 | max. 3 x 480 Vac | 1200 A | 5 % @ 480 Vac | |
LR3 48-3/1400 | max. 3 x 480 Vac | 1400 A | 3 % @ 480 Vac | |
LR3 48-5/1400 | max. 3 x 480 Vac | 1400 A | 5 % @ 480 Vac | |
LR3 48-3/1600 | max. 3 x 480 Vac | 1600 A | 3 % @ 480 Vac | |
LR3 48-5/1600 | max. 3 x 480 Vac | 1600 A | 5 % @ 480 Vac |
Or do you have different requirements?
We can help you!
NKE 230 / 400
Line reactor, single-phase
230 / 400 Vac, 4 – 25 A, 1.170 - 12.750 mH, Power harmonic damping
Version | Rated voltage | Rated current | ||
---|---|---|---|---|
NKE 2/14,65 | max. 230 Vac | 2 A | ||
NKE 2/25,50 | max. 400 Vac | 2 A | ||
NKE 4/7,33 | max. 230 Vac | 4 A | ||
NKE 4/12,75 | max. 400 Vac | 4 A | ||
NKE 6/4,88 | max. 230 Vac | 6 A | ||
NKE 6/8,50 | max. 400 Vac | 6 A | ||
NKE 10/2,93 | max. 230 Vac | 10 A | ||
NKE 10/5,10 | max. 400 Vac | 10 A | ||
NKE 16/1,83 | max. 230 Vac | 16 A | ||
NKE 16/3,19 | max. 400 Vac | 16 A | ||
NKE 20/1,47 | max. 230 Vac | 20 A | ||
NKE 20/2,55 | max. 400 Vac | 20 A | ||
NKE 25/1,17 | max. 230 Vac | 25 A | ||
NKE 25/2,04 | max. 400 Vac | 25 A | ||
NKE 35/0,84 | max. 230 Vac | 35 A | ||
NKE 35/1,46 | max. 400 Vac | 35 A | ||
NKE 40/0,73 | max. 230 Vac | 40 A | ||
NKE 40/1,28 | max. 400 Vac | 40 A | ||
NKE 50/0,59 | max. 230 Vac | 50 A | ||
NKE 50/1,02 | max. 400 Vac | 50 A | ||
NKE 63/0,49 | max. 230 Vac | 63 A | ||
NKE 63/0,81 | max. 400 Vac | 63 A | ||
NKE 100/0,29 | max. 230 Vac | 100 A | ||
NKE 125/0,23 | max. 230 Vac | 125 A |
Or do you have different requirements?
We can help you!
Version | |||
---|---|---|---|
COV 300x200x108 | |||
COV 425x185x108 | |||
COV 480x200x108 | |||
COV 480x265x108 | |||
COV 510x235x120 | |||
COV 510x260x120 | |||
COV 586x275x120 |
Or do you have different requirements?
We can help you!