USTE 800/2x115
Control- and isolating transformer
Rated input voltage
208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac
Rated output voltage
2 x 115 Vac
Rated power VDE (DB cos phi=1)
800 VA
Version | Rated input voltage | Rated output voltage | Rated power VDE (DB cos phi=1) | |
---|---|---|---|---|
USTE 40/2x12 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 12 Vac | 40 VA | |
USTE 100/2x12 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 12 Vac | 100 VA | |
USTE 100/2x115 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 115 Vac | 100 VA | |
USTE 250/2x12 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 12 Vac | 250 VA | |
USTE 250/2x115 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 115 Vac | 250 VA | |
USTE 400/2x12 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 12 Vac | 400 VA | |
USTE 400/2x115 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 115 Vac | 400 VA | |
USTE 630/2x12 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 12 Vac | 630 VA | |
USTE 630/2x115 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 115 Vac | 630 VA | |
USTE 800/2x115 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 115 Vac | 800 VA | |
USTE 1000/2x115 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 115 Vac | 1,000 VA | |
USTE 1200/2x115 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 115 Vac | 1,200 VA | |
USTE 1600/2x115 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 115 Vac | 1,600 VA | |
USTE 2500/2x115 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 115 Vac | 2,500 VA | |
USTE 3200/2x115 | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac | 2 x 115 Vac | 3,200 VA |
Technical data for USTE 800/2x115
Input | |
---|---|
Rated input voltage | 208 Vac/ 230 Vac/ 380 Vac/ 400 Vac/ 415 Vac/ 440 Vac/ 460 Vac/ 480 Vac/ 500 Vac/ 525 Vac/ 550 Vac/ 575 Vac/ 600 Vac |
Rated frequency | 50 - 60 Hz |
Output | |
---|---|
Rated output voltage | 2 x 115 Vac |
Rated power VDE (DB cos phi=1) | 800 VA |
Rated power VDE (KB cos phi=0.5) | 3,400 VA |
No-load voltage (app. x factor) | 1.03 |
Efficiency | 93.0 % |
Standards | |
---|---|
Classification | Control- and isolating transformer |
Approvals | |
---|---|
Approvals | cULus |
Environment | |
---|---|
Ambient temperature max. | 40 °C |
Type of cooling | self-cooling |
Safety and protection | |
---|---|
Type | Open type |
Insulation class | VDE=B, UL=class 130 |
Protection index | IP 00 |
Safety class (prepared) | I |
Short circuit strength | non-short-circuit proof |
PRI Fusing recommendation by circuit breaker with tripping characteristic type 20 x Irated related to set) | |
---|---|
Setting range 208 - 230 Vac | 2.50 - 4.00 A |
Setting value 208 - 230 Vac | 3.90 A |
Setting range 380 - 415 Vac | 1.60 - 2.50 A |
Setting value 380 - 415 Vac | 2.20 A |
Setting range 440 +20 Vac | 1.60 - 2.50 A |
Setting value 440 +20 Vac | 1.90 A |
Setting range 500 -20/+25 Vac | 1.60 - 2.50 A |
Setting value 500 -20/+25 Vac | 1.70 A |
Setting range 575 ±25 Vac | 1.00 - 1.60 A |
Setting value 575 ±25 Vac | 1.50 A |
Terminal and mounting | |
---|---|
Fixing method | Base plate |
Fixing screws | M6 |
Terminals Input | push-in terminals, 4 mm² |
Terminals Output | push-in terminals, 4 mm² |
Terminals PE | Tab connector, 6.3 x 0.8 mm |
Measures and weights | |
---|---|
Depth | 136 mm |
Height | 146 mm |
Width | 150 mm |
Weight | 10.9 kg |
Info on USTE series
General Data
- Insulation class B
- Rated power 100 - 3,200 VA
- Maximum ambient temperature 40 °C
- Efficiency up to 96 %
- Degree of protection IP 00
- Rated output voltage 2 x 12 – 2 x 115 Vac
- Rated input voltage 208 - 600 Vac
Benefits
- Universal input voltages 208 to 600 Vac
- Very good switch-on behaviour thanks to reduced starting currents
- High power density due to a compact construction design
- Up to 250 VA with combination footplate for bolted and rail mounting
- Simple mounting thanks to robust metal footplate with oval slots
- Contact protected screw connection terminals complying with UVV BGV A3
- Quick to cable up thanks to the use of push-in terminals
- Very good corrosion protection and low noise thanks to BLOCK IMPEX vacuum impregnation