HF1P 4,60-230
Harmonic Filter HF1P 230
Version HF1P 4,60-230
Rated voltage
230 Vac
Rated current
20.00 A
Rated load power*
4.6 kW
Version | Rated voltage | Rated current | Rated load power* | |
---|---|---|---|---|
HF1P 0,19-230 | 230 Vac | 0.84 A | 0.19 kW | |
HF1P 0,59-230 | 230 Vac | 2.50 A | 0.59 kW | |
HF1P 1,01-230 | 230 Vac | 4.44 A | 1.01 kW | |
HF1P 2,73-230 | 230 Vac | 11.90 A | 2.73 kW | |
HF1P 3,68-230 | 230 Vac | 16.00 A | 3.68 kW | |
HF1P 4,60-230 | 230 Vac | 20.00 A | 4.6 kW | |
HF1P 5,70-230 | 230 Vac | 25.00 A | 5.50 kW |
DOWNLOADS
Technical files
data sheet
Approvals / Manufacturer's declaration
EU-Declaration of Conformity
Technical data for HF1P 4,60-230
Operating data | |
---|---|
Rated voltage | 230 Vac |
Voltage range | 207-253 Vac |
Rated current | 20.00 A |
THD-I | 10 % at 50 Hz, 18 % at 60 Hz (nominal load) |
Rated load power* | 4.6 kW |
Description of the load | Symmetrical loading by converters with B2U input rectifiers |
Overrating Capacity | 150 % for 60 sec. every 10 min. |
Efficiency | 98.2 % |
Power loss | 80.0 W |
Capacitive idle power | 3.3 kVAr |
Input | |
---|---|
Rated frequency | 50 - 60 Hz |
Environment | |
---|---|
Ambient temperature | -10 °C to +40 °C, without condensation |
Type of cooling | AN |
MTBF @ 50 °C/500 V (Mil-HB-217F) | >500.000 h @ 40°C/400Vac |
Safety and protection | |
---|---|
Type | Metal enclosure |
Insulation class | H |
Protection index | IP 20 |
Safety class | I |
Terminal and mounting | |
---|---|
Terminals phase | Screw clamp, 16 mm² |
Terminals PE | Bolt, M6 |
Fixing method | Mounting lugs |
Measures and weights | |
---|---|
Depth | 444 mm |
Height | 210 mm |
Width | 144 mm |
Weight | 22.2 kg |
Notes | |
---|---|
* | IE2 efficiencies of the motors and an efficiency >96 % assumed |
Info on HF1P 230 series
General Data
- Degree of protection IP 20
- Load rated capacity 0.19 - 5.7 kW
- THD-I 10 % at 50 Hz, 18 % at 60 Hz in rated operation
- Rated current 0,84 - 25 A
- Rated voltage 230 Vac
- Ambient temperature -10 °C to +40 °C
- Insulation class H
Benefits
- Use of the HF1P as a central sum filter for multiple converters possible
- Operation at 50 - 60 Hz possible
- Power factor >0,95 at rated current
- Support in the compliance with IEEE 519, D-A-CH-CZ
- Compliance with EN 61000-3-2, EN 61000-3-12
- Sinusoidal current consumption from the main in devices with uncontrolled B2U diode rectifiers