HF1K 100-400

Harmonic filter HF1K 400

Version HF1K 100-400
Rated voltage 3 x 400 Vac Rated current 3 x 144 A Rated load power* 90 kW
Version Rated voltage Rated current Rated load power*
HF1K 7-400 3 x 400 Vac 3 x 10 A 5.5 kW
HF1K 13-400 3 x 400 Vac 3 x 19 A 11 kW
HF1K 18-400 3 x 400 Vac 3 x 26 A 15 kW
HF1K 24-400 3 x 400 Vac 3 x 35 A 20 kW
HF1K 30-400 3 x 400 Vac 3 x 43 A 26 kW
HF1K 50-400 3 x 400 Vac 3 x 73 A 45 kW
HF1K 70-400 3 x 400 Vac 3 x 101 A 63 kW
HF1K 100-400 3 x 400 Vac 3 x 144 A 90 kW
Image of %s BLOCK Item: HF1K 100-400

Technical data for HF1K 100-400

Operating data
Rated voltage 3 x 400 Vac
Voltage range 360-440 Vac
Rated current 3 x 144 A
THD-I 8 % (nominal load)
Rated load power* 90 kW
Description of the load Symmetrical loading by converters with B6U input rectifiers
Overrating Capacity 150 % for 60 sec. every 10 min.
Efficiency 99.0 %
Power loss 750.0 W
Capacitive idle power 19.0 kVAr
Input
Rated frequency 50 - 60 Hz
Approvals
Approvals cURus
Environment
Ambient temperature -10 °C to +45 °C,
without condensation
Type of cooling AN
MTBF @ 50 °C/500 V (Mil-HB-217F) >500.000 h
@ 40°C/400Vac
Safety and protection
Type Open type
Insulation class H
Protection index IP 00
Safety class I
Terminal and mounting
Terminals phase Copper tab, M12 bolt
Terminals PE Bolt, M8
Fixing method Mounting lugs
Measures and weights
Depth 375 mm
Height 430 mm
Width 685 mm
Weight 163.0 kg
Notes
* IE2 efficiencies of the motors and an efficiency
>96 % assumed

Info on HF1K 400 series

General Data
  • Degree of protection IP 00
  • Load rated capacity 5.5 - 90 kW
  • Ambient temperature -10 °C to +45 °C
  • Insulation class H
  • Rated voltage 3 x 400 Vac
  • THD-I <8 % in rated operation
  • Rated current 3 x 10 - 3 x 144 A
Benefits
  • Harmonic filter with minimum capacitive idle reactive power
  • Use of the HF1K as a central sum filter for multiple converters possible
  • Sinusoidal current consumption from the main in devices with uncontrolled B6U diode rectifiers
  • Compliance with EN 61000-3-2, EN 61000-3-12
  • Support in the compliance with IEEE 519, D-A-CH-CZ
  • Cos(phi)>0,95 at rated current
  • Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor
  • Operation at 50 - 60 Hz possible
  • Very good corrosion protection and low noise thanks to vacuum impregnation

Our recommendations for you

BLOCK product: HLD 110-500/180
HLD 110-500/180
Radio interference suppression filter, three-phase
3 x 520 Vac, 3 x 8 – 3 x 250 A, Leakage current 20.00 - 37.00 mA, For enhanced requirements
to accessory part
BLOCK product: LR3 40-4/160
LR3 40-4/160
Line reactor, three-phase
3 x 400 Vac, 3 x 2 – 3 x 1600 A, 0.019 – 18.500 mH, Use as line reactor, commutating reactor or PFC reactor
to accessory part