HFM-FB 34-480

Harmonic filter HFM-FB 480

Version HFM-FB 34-480
Rated voltage max. 3 x 480 Vac Rated current 3 x 43.00 A Rated load power 40.23 HP
Version Rated voltage Rated current Rated load power
HFM-FB 8-480 max. 3 x 480 Vac 3 x 10.00 A 7.38 HP
HFM-FB 15-480 max. 3 x 480 Vac 3 x 19.00 A 14.75 HP
HFM-FB 21-480 max. 3 x 480 Vac 3 x 26.00 A 20.12 HP
HFM-FB 28-480 max. 3 x 480 Vac 3 x 35.00 A 29.50 HP
HFM-FB 34-480 max. 3 x 480 Vac 3 x 43.00 A 40.23 HP
HFM-FB 57-480 max. 3 x 480 Vac 3 x 72.00 A 60.35 HP
HFM-FB 80-480 max. 3 x 480 Vac 3 x 101.00 A 73.76 HP
HFM-FB 115-480 max. 3 x 480 Vac 3 x 144.00 A 120.69 HP
HFM-FB 145-480 max. 3 x 480 Vac 3 x 180.00 A 147.51 HP
HFM-FB 175-480 max. 3 x 480 Vac 3 x 217.00 A 177.01 HP
HFM-FB 230-480 max. 3 x 480 Vac 3 x 289,00 A 214.56 HP
HFM-FB 260-480 max. 3 x 480 Vac 3 x 325,00 A 308.44 HP
HFM-FB 295-480 max. 3 x 480 Vac 3 x 370,00 A 348.67 HP

Technical Data for HFM-FB 34-480

Operating data
Rated current 3 x 43.00 A
Rated voltage max. 3 x 480 Vac
Rated frequency 60 Hz
THD-I 7 % typ at nominal load
Rated load power 40.23 HP
Description of the load Balanced load by inverter
Overrating Capacity 150 % for 60 sec. every 10 min.
Efficiency 99 %
Approvals
Approvals cURus
Environment
Ambient temperature 14 °F to +104 °F,
without condensation
MTBF @ 122 °F/500 V (Mil-HB-217F) >200.000 h
Safety and protection
Type Metal enclosure
Insulation class IEC=F, UL=class 155
Protection index IP 00
Safety class I
SCCR 100 kA
Terminal and mounting
Connection type for M8
Fixing method Mounting lugs
Measures and weights
Depth 14.06 inch
Height 8.86 inch
Width 34.84 inch
Weight 123.46 lbs
Notes
* IE2 efficiencies of the motors and an efficiency
>96 % assumed

Information for HFM-FB 480 series

General Data
  • Power range 10 to 384 HP
  • SCCR 100 kA (without preliminary fuse)
  • Degree of protection IP 00
  • Ambient temperature 14 °F / -10 °C to +104 °F / +40 °C
  • Insulation class F
  • THD-I 7 % typ. at nominal load
  • Rated current 3 x 10.00 - 3 x 433.00 A
  • Rated voltage 3 x 400 - 3 x 480 Vac
Benefits
  • Compliance with EN 61000-3-2, EN 61000-3-12
  • Sinusoidal current consumption from the main in devices with uncontrolled B6U diode rectifiers or controlled B6C thyristor bridges
  • Use of the HFM as a central hum filter for multiple converters possible
  • Support in the compliance with IEEE 519, D-A-CH-CZ
  • Power factor >0.95 at rated current
  • Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor

Our recommendations for you

BLOCK product: LR3 48-5/30
LR3 48-5/30
Line reactor, three-phase
3 x 480 Vac, 3 x 2 – 3 x 1600 A, 0.014 - 18.500 mH, Use as line reactor, commutating reactor or PFC reactor
View accessory
BLOCK product: LR3 48-3/30
LR3 48-3/30
Line reactor, three-phase
3 x 480 Vac, 3 x 2 – 3 x 1600 A, 0.014 - 18.500 mH, Use as line reactor, commutating reactor or PFC reactor
View accessory
BLOCK product: HLD 110-500/30
HLD 110-500/30
Radio interference suppression filter, three-phase
3 x 520 Vac, 3 x 8 – 3 x 250 A, Leakage current 20.00 to 37.00 mA, For enhanced EMI suppression
View accessory