HFD 210-500/130
Radio interference suppression filter HFD 210
Version HFD 210-500/130
Rated voltage
3 x 520 Vac
Rated current
3 x 130 A
Leakage current (50 Hz)*
18 mA
Version | Rated voltage | Rated current | Leakage current (50 Hz)* | |
---|---|---|---|---|
HFD 210-500/7 | 3 x 520 Vac | 3 x 7 A | 13 mA | |
HFD 210-500/16 | 3 x 520 Vac | 3 x 16 A | 14 mA | |
HFD 210-500/30 | 3 x 520 Vac | 3 x 30 A | 16 mA | |
HFD 210-500/42 | 3 x 520 Vac | 3 x 42 A | 16 mA | |
HFD 210-500/55 | 3 x 520 Vac | 3 x 55 A | 16 mA | |
HFD 210-500/75 | 3 x 520 Vac | 3 x 75 A | 16 mA | |
HFD 210-500/100 | 3 x 520 Vac | 3 x 100 A | 16 mA | |
HFD 210-500/130 | 3 x 520 Vac | 3 x 130 A | 18 mA | |
HFD 210-500/180 | 3 x 520 Vac | 3 x 180 A | 18 mA |
DOWNLOADS
Technical files
Data sheet
Approvals / Manufacturer's declaration
Manufacturer's declaration to EN 60939-2
COC CSA 22.2
Technical Data for HFD 210-500/130
Operating data | |
---|---|
Rated voltage | 3 x 520 Vac |
Voltage range | 0 - 3 x 520 Vac |
Rated current | 3 x 130 A |
Leakage current (50 Hz)* | 18 mA |
Leakage current (50 Hz)** | 173 mA |
Rated frequency | 50 - 60 Hz |
Overrating Capacity | 150 %, shortly |
Approvals | |
---|---|
Approvals | cURus, UL 1283 5th edition, CSA 22.2 No.8 |
Environment | |
---|---|
Ambient temperature max. | 122.0 °F |
Climatic category | 25/085/21 [in accordance with EN 60068-1] |
Safety and protection | |
---|---|
Type | Metal enclosure |
Protection index | IP 20 |
Safety class (prepared) | I |
Test voltage | 2150 Vdc Phase/Phase, 2700 Vdc Phase/PE |
Terminal and mounting | |
---|---|
Terminals phase | Screw clamp, 50 mm² |
Connection type | Bolt, M10 |
Fixing method | Mounting lugs |
Measures and weights | |
---|---|
Width | 16.89 inch |
Height | 9.45 inch |
Depth | 4.33 inch |
Weight | 14.99 lbs |
Notes | |
---|---|
* | Leakage current measured against the maximum permissible input voltage fluctuation in accordance with IEC 38 ±10 % |
** | Leakage current by loss of two phases |
Information for HFD 210 series
General Data
- Degree of protection IP 20
- Rated voltage 3 x 520 Vac
- Leakage current 13.00 - 18.00 mA
- Voltage range 0 - 3 x 480 - 520 Vac
- Rated current 3 x 7 - 3 x 180 A
Benefits
- Increase in the interference immunity of the connected equipment
- Efficient filter effect against line-bound interference emissions
- Two-stage filter concept
- For enhanced EMI suppression