HF1K 13-480-0
Harmonic filter HF1K 480
Version HF1K 13-480-0
Rated voltage
3 x 480 Vac
Rated current
3 x 19 A
Rated load power
14.3 HP
Version | Rated voltage | Rated current | Rated load power | |
---|---|---|---|---|
HF1K 7-480-0 | 3 x 480 Vac | 3 x 10 A | 7.5 HP | |
HF1K 13-480-0 | 3 x 480 Vac | 3 x 19 A | 14.3 HP | |
HF1K 18-480-0 | 3 x 480 Vac | 3 x 26 A | 19.5 HP | |
HF1K 24-480-0 | 3 x 480 Vac | 3 x 35 A | 26 HP | |
HF1K 30-480-0 | 3 x 480 Vac | 3 x 43 A | 33.8 HP | |
HF1K 70-480-0 | 3 x 480 Vac | 3 x 102 A | 81.9 HP | |
HF1K 100-480-0 | 3 x 480 Vac | 3 x 144 A | 117 HP |
DOWNLOADS
Approvals / Manufacturer's declaration
COA UL 508 & CSA 22.2
COC UL 508 & CSA 22.2
EU-Declaration of Conformity
Additional information
Harmonic Filter brochure
Technical Data for HF1K 13-480-0
Operating data | |
---|---|
Rated voltage | 3 x 480 Vac |
Rated current | 3 x 19 A |
THD-I | 8 % (nominal load) |
Rated load power | 14.3 HP |
Description of the load | Symmetrical loading by converters with B6U input rectifiers |
Overrating Capacity | 150 % for 60 sec. every 10 min. |
Efficiency | 99 % |
Power loss | 160 W |
Capacitive idle power | 22 kVAr |
Input | |
---|---|
Rated frequency | 50 - 60 Hz |
Approvals | |
---|---|
Approvals | cURus |
Environment | |
---|---|
Ambient temperature | 14 °F to +113 °F, without condensation |
Type of cooling | Air natural |
MTBF @ 122 °F/500 V (Mil-HB-217F) | >500.000 h @ 104 °F / 480 Vac |
Safety and protection | |
---|---|
Type | Open type |
Insulation class | H |
Protection index | IP 00 |
Safety class | I |
Terminal and mounting | |
---|---|
Terminals phase | Screw clamp, 10 mm² |
Connection type | Bolt, M6 |
Fixing method | Mounting lugs |
Measures and weights | |
---|---|
Depth | 10.83 inch |
Height | 10.83 inch |
Width | 17.32 inch |
Weight | 61.73 lbs |
Notes | |
---|---|
* | IE2 efficiencies of the motors and an efficiency >96 % assumed |
Information for HF1K 480 series
General Data
- Degree of protection IP 00
- Rated load power 7.5 - 120 HP (5,5 kW - 90 kW)
- Ambient temperature 14 °F / -10 °C to +113 °F / +45 °C
- Insulation class H
- THD-I <8 % in rated operation
- Rated current 3 x 10 - 3 x 144 A
- Rated voltage 3 x 480 Vac
Benefits
- Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor
- Use of the HF1K as a central hum filter for multiple converters possible
- Sinusoidal current consumption from the main in devices with uncontrolled B6U diode rectifiers
- Support compliance with EN 61000-3-2, EN 61000-3-12
- Support compliance with IEEE 519, D-A-CH-CZ
- Power factor >0.95 at rated current
- Operation at 50 - 60 Hz possible
- Harmonic filter with minimum capacitive reactive power
- Very good corrosion protection and low noise thanks to vacuum impregnation