HF1K 100-480-0

Harmonic filter HF1K 480

Version HF1K 100-480-0
Rated voltage 3 x 480 Vac Rated current 3 x 144 A Rated load power 117 HP
Version Rated voltage Rated current Rated load power
HF1K 7-480-0 3 x 480 Vac 3 x 10 A 7.5 HP
HF1K 13-480-0 3 x 480 Vac 3 x 19 A 14.3 HP
HF1K 18-480-0 3 x 480 Vac 3 x 26 A 19.5 HP
HF1K 24-480-0 3 x 480 Vac 3 x 35 A 26 HP
HF1K 30-480-0 3 x 480 Vac 3 x 43 A 33.8 HP
HF1K 70-480-0 3 x 480 Vac 3 x 102 A 81.9 HP
HF1K 100-480-0 3 x 480 Vac 3 x 144 A 117 HP

Technical Data for HF1K 100-480-0

Operating data
Rated voltage 3 x 480 Vac
Rated current 3 x 144 A
THD-I 8 % (nominal load)
Rated load power 117 HP
Description of the load Symmetrical loading by converters with B6U input rectifiers
Overrating Capacity 150 % for 60 sec. every 10 min.
Efficiency 99 %
Power loss 750 W
Capacitive idle power 228 kVAr
Input
Rated frequency 50 - 60 Hz
Approvals
Approvals cURus
Environment
Ambient temperature 14 °F to +113 °F,
without condensation
Type of cooling Air natural
MTBF @ 122 °F/500 V (Mil-HB-217F) >500.000 h
@ 104 °F / 480 Vac
Safety and protection
Type Open type
Insulation class H
Protection index IP 00
Safety class I
Terminal and mounting
Terminals phase Copper tab, M12 bolt
Connection type Bolt, M8
Fixing method Mounting lugs
Measures and weights
Depth 14.76 inch
Height 16.93 inch
Width 26.97 inch
Weight 359.35 lbs
Notes
* IE2 efficiencies of the motors and an efficiency
>96 % assumed

Information for HF1K 480 series

General Data
  • Degree of protection IP 00
  • Rated load power 7.5 - 120 HP (5,5 kW - 90 kW)
  • Ambient temperature 14 °F / -10 °C to +113 °F / +45 °C
  • Insulation class H
  • THD-I <8 % in rated operation
  • Rated current 3 x 10 - 3 x 144 A
  • Rated voltage 3 x 480 Vac
Benefits
  • Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor
  • Use of the HF1K as a central hum filter for multiple converters possible
  • Sinusoidal current consumption from the main in devices with uncontrolled B6U diode rectifiers
  • Support compliance with EN 61000-3-2, EN 61000-3-12
  • Support compliance with IEEE 519, D-A-CH-CZ
  • Power factor >0.95 at rated current
  • Operation at 50 - 60 Hz possible
  • Harmonic filter with minimum capacitive reactive power
  • Very good corrosion protection and low noise thanks to vacuum impregnation

Our recommendations for you

BLOCK product: HLD 110-500/180
HLD 110-500/180
Radio interference suppression filter, three-phase
3 x 520 Vac, 3 x 8 – 3 x 250 A, Leakage current 20.00 to 37.00 mA, For enhanced EMI suppression
View accessory
BLOCK product: LR3 48-3/160
LR3 48-3/160
Line reactor, three-phase
3 x 480 Vac, 3 x 2 – 3 x 1600 A, 0.014 - 18.500 mH, Use as line reactor, commutating reactor or PFC reactor
View accessory