EB-PT2-0
2-pole physical isolation EB-PT2-0
Input rated voltage
24 Vdc
Output rated voltage
24 Vdc
Version | Input rated voltage | Output rated voltage | |
---|---|---|---|
EB-PT2-0 | 24 Vdc | 24 Vdc |
DOWNLOADS
Approvals / Manufacturer's declaration
EU-Declaration of Conformity
Additional information
Brochure EasyB
Technical Data for EB-PT2-0
Input | |
---|---|
Input rated voltage | 24 Vdc |
Input voltage range | 18 – 30 Vdc |
Max. total input current | 6 A |
Control level | >15 V - ON; < 10 V - OFF |
Current consumption control input | 0.15 mA @ 24 Vdc |
Output | |
---|---|
Output rated voltage | 24 Vdc |
Maximum voltage drop between input and output | 273 mV |
Resistance to reverse feed max. | 35 Vdc |
Environment | |
---|---|
Ambient temperature | -40 °F to +158 °F |
Type of cooling | Natural convection |
Required minimum spacing (over/under) | 1.18 inch |
Safety and protection | |
---|---|
Protection index | IP 20 |
Degree of pollution | 2 |
Terminal and mounting | |
---|---|
24 V Output terminals | "OUT +" 2 x 0.08 – 2.5 mm² |
0 V Output terminal | "OUT -" 2 x 0.08 – 2.5 mm² |
0 V Input terminal | "IN -" 2 x 0.08 – 2.5 mm² |
Terminals Control input | "OK" 2 x 0.08 – 2.5 mm² |
Mounting position | horizontal for standard rail DIN TS35 |
Measures and weights | |
---|---|
Width | 0.47 inch |
Height | 3.90 inch |
Depth | 2.36 inch |
Weight | 0.13 lbs |
Information for EB-PT2-0 series
General Data
- Input rated voltage 24 Vdc
- Protection index IP 20
- Output rated voltage 24 Vdc
- Ambient temperature -13 °F / -25 °C ... +158 °F / +70 °C
Benefits
- Two-pole physical isolation with galvanic isolation, to be added to the right side of circuit breaker channels with single alarm signal.
- Use for tripping currents up to 6 A
- All functions of the circuit breaker (communication, characteristics) can be used continuously.