TTML 4000/230 - no longer available
Isolating transformer for supply of medical rooms TTML
Version TTML 4000/230 - no longer available
Rated input voltage
230 Vac
Rated output voltage
115 and 230 Vac
Rated Power
4,000 VA
Version | Rated input voltage | Rated output voltage | Rated Power | |
---|---|---|---|---|
TTML 3150/230 - no longer available | 230 Vac | 115 and 230 Vac | 3,150 VA | |
TTML 4000/230 - no longer available | 230 Vac | 115 and 230 Vac | 4,000 VA | |
TTML 5000/230 - no longer available | 230 Vac | 115 and 230 Vac | 5,000 VA | |
TTML 6300/230 - no longer available | 230 Vac | 115 and 230 Vac | 6,300 VA | |
TTML 8000/230 - no longer available | 230 Vac | 115 and 230 Vac | 8,000 VA |
Technical data for TTML 4000/230 - no longer available
Input | |
---|---|
Rated input voltage | 230 Vac |
Low-inrush current | ≤12 x INom |
Rated frequency | 50 - 60 Hz |
Output | |
---|---|
Rated output voltage | 115 and 230 Vac |
Rated Power | 4,000 VA |
Short circuit voltage | ≤3 % |
No-load current | ≤3 % |
Efficiency | 97.0 % |
Environment | |
---|---|
Ambient temperature max. | 40 °C |
Safety and protection | |
---|---|
Type | Open type |
Insulation class | B |
Protection index | IP 00 |
Safety class (prepared) | II |
Short circuit strength | non-short-circuit proof |
Test voltage | 3.75 kVac |
Terminal and mounting | |
---|---|
Terminals | Screw-type terminal 10 mm², Screw-type terminal 4 mm² |
Fixing method | Fixing rail |
Fixing screws | M8 |
Measures and weights | |
---|---|
Width | 275 mm |
Height | 200 mm |
Depth | 350 mm |
Weight | 55.00 kg |
Info on TTML series
General Data
- Insulation class B
- Rated input voltage 230 Vac
- Rated output voltage 115 and 230 Vac
- Rated power 3,150 - 8,000 VA
- Maximum ambient temperature 40 °C
- Efficiency up to 97 %
- Degree of protection IP 00
Benefits
- Very high efficiency
- Contact protected screw connection terminals complying with UVV BGV A3
- Very low short circuit voltage
- Very good switch-on behaviour thanks to reduced starting currents
- PTC resistor built into every coil to set up an external monitoring unit for protection against overload
- Safe galvanic isolation
- Low height
- Very low idle current
- Very good corrosion protection and low noise thanks to BLOCK IMPEX vacuum impregnation