PEL 230 – Single-phase switched mode power supply
Input rated voltage
100 - 240 Vac
Output rated voltage
24 Vdc
Output rated current
4.00 A
Version | Input rated voltage | Output rated voltage | Output rated current | |
---|---|---|---|---|
PEL 230/5-5,5 | 100 - 240 Vac | 5 Vdc | 5.50 A | |
PEL 230/12-2 | 100 - 240 Vac | 12 Vdc | 2.00 A | |
PEL 230/12-4 | 100 - 240 Vac | 12 Vdc | 4.00 A | |
PEL 230/12-6,5 | 100 - 240 Vac | 12 Vdc | 6.50 A | |
PEL 230/18-1,1 | 100 - 240 Vac | 18 Vdc | 1.10 A | |
PEL 230/18-2,5 | 100 - 240 Vac | 18 Vdc | 2.50 A | |
PEL 230/24-1,3 | 100 - 240 Vac | 24 Vdc | 1.30 A | |
PEL 230/24-2,5 | 100 - 240 Vac | 24 Vdc | 2.50 A | |
PEL 230/24-4 | 100 - 240 Vac | 24 Vdc | 4.00 A |
DOWNLOADS
Technical files
Instruction manual
Approvals / Manufacturer's declaration
UL 508 Listed USA (E219022)
UL 508 Listed Canada (E219022)
COC UL 508 & CSA 22.2
Marine DNV GL (TAA00000KN)
EU-Declaration of Conformity
Technical data for PEL 230/24-4
Input | |
---|---|
Input rated voltage | 100 - 240 Vac |
Input voltage range | 85 - 264 Vac (120 - 373 Vdc) |
Input rated current (rated load) | 1.6 / 0.9 A (110 / 230 Vac) |
Rated frequency range | 44 - 66 Hz / 0 Hz |
Starting current limiter | <30 A, NTC |
Input fuse internal | 4 A |
Recommended back-up fuse (circuit breaker) | 6 A, 10 A, 16 A, characteristics B, C |
Mains buffering (rated load) | 15 / 100 ms |
Transient surge voltage protection | Varistor |
Output | |
---|---|
Output rated voltage | 24 Vdc |
Output voltage range | 22,8 - 26,4 Vdc |
Output rated current | 4.00 A |
Resistance to reverse feed max. | 30 Vdc |
Overload behaviour | Constant current |
Ripple factor | typ. 100 mVss |
Parallel connection | Yes |
Serial operation | Yes |
Efficiency | typ. 88 % |
Signaling | |
---|---|
Power Good (DC OK) | LED green |
Approvals | |
---|---|
Approvals | cURus, cULus, GL |
Environment | |
---|---|
Ambient temperature | -25 °C to +55 °C |
Storage temperature | -25 °C to +85 °C |
Derating | -3 %/K > +45 °C |
Current capacity by any mounting position | max. 2.4 A |
Safety and protection | |
---|---|
Protection index | IP 20 |
Safety class | II, (in closed cabinet) |
Terminal and mounting | |
---|---|
Terminals input, (spring clamp terminal) | max. 2.5 mm² |
Terminals output, (spring clamp terminal) | max. 2.5 mm² |
Mounting position | vertical |
Fixing method | DIN rail system TS35 |
Measures and weights | |
---|---|
Width | 90 mm |
Height | 89 mm |
Depth | 59 mm |
Weight | 0.30 kg |
Info on PEL 230 series
General Data
- Ambient temperature -25 °C to +55 °C
- Protection index IP 20
- Efficiency up to 88 %
- Output rated voltage 5 - 18 Vdc
- Output rated current 1.1 - 6.5 A
- Input voltage range 85 - 264 Vac
Benefits
- Panel installation on mounting rails
- Stabilised and adjustable output voltage
- DC OK signalling via LEDs
- Parallel connection option
- Service-friendly spring-loaded connector system
- 3 years warranty