HF1K 70-480-0

Harmonic filter HF1K 480

Version HF1K 70-480-0
Rated voltage 3 x 480 Vac Rated current 3 x 102 A Rated load power* 63 kW
Version Rated voltage Rated current Rated load power*
HF1K 7-480-0 3 x 480 Vac 3 x 10 A 5.5 kW
HF1K 13-480-0 3 x 480 Vac 3 x 19 A 11 kW
HF1K 18-480-0 3 x 480 Vac 3 x 26 A 15 kW
HF1K 24-480-0 3 x 480 Vac 3 x 35 A 20 kW
HF1K 30-480-0 3 x 480 Vac 3 x 43 A 26 kW
HF1K 70-480-0 3 x 480 Vac 3 x 102 A 63 kW
HF1K 100-480-0 3 x 480 Vac 3 x 144 A 90 kW

Technical data for HF1K 70-480-0

Operating data
Rated voltage 3 x 480 Vac
Rated current 3 x 102 A
THD-I 8 % (nominal load)
Rated load power* 63 kW
Description of the load Symmetrical loading by converters with B6U input rectifiers
Overrating Capacity 150 % for 60 sec. every 10 min.
Efficiency 99.0 %
Power loss 550.0 W
Capacitive idle power 162.0 kVAr
Input
Rated frequency 50 - 60 Hz
Approvals
Approvals cURus
Environment
Ambient temperature -10 °C to +45 °C,
without condensation
Type of cooling AN
MTBF @ 50 °C/500 V (Mil-HB-217F) >500.000 h
@ 104 °F / 480 Vac
Safety and protection
Type Open type
Insulation class H
Protection index IP 00
Safety class I
Terminal and mounting
Terminals phase Copper tab, M12 bolt
Terminals PE Bolt, M8
Fixing method Mounting lugs
Measures and weights
Depth 348 mm
Height 420 mm
Width 685 mm
Weight 125.0 kg
Notes
* IE2 efficiencies of the motors and an efficiency
>96 % assumed

Info on HF1K 480 series

General Data
  • Degree of protection IP 00
  • Load rated capacity 7.5 - 120 HP (5,5 kW - 90 kW)
  • Ambient temperature -10 °C to +45 °C
  • Insulation class H
  • THD-I <8 % in rated operation
  • Rated current 3 x 10 - 3 x 144 A
  • Rated voltage 3 x 480 Vac
Benefits
  • Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor
  • Use of the HF1K as a central sum filter for multiple converters possible
  • Sinusoidal current consumption from the main in devices with uncontrolled B6U diode rectifiers
  • Compliance with EN 61000-3-2, EN 61000-3-12
  • Support in the compliance with IEEE 519, D-A-CH-CZ
  • Cos(phi)>0,95 at rated current
  • Operation at 50 - 60 Hz possible
  • Harmonic filter with minimum capacitive idle reactive power
  • Very good corrosion protection and low noise thanks to vacuum impregnation

Our recommendations for you

BLOCK product: HLD 110-500/100
HLD 110-500/100
Radio interference suppression filter, three-phase
3 x 520 Vac, 3 x 8 – 3 x 250 A, Leakage current 20.00 - 37.00 mA, For enhanced requirements
to accessory part
BLOCK product: LR3 48-3/115
LR3 48-3/115
Line reactor, three-phase
3 x 480 Vac, 3 x 2 – 3 x 1600 A, 0.014 - 18.500 mH, Use as line reactor, commutating reactor or PFC reactor
to accessory part