Harmonic filter HF1K 480

Harmonic filter HF1K 480, HF1K 480
Data Standards/Certifications Applications Downloads
General Data
  • Rated voltage 3 x 480 Vac
  • Rated current 3 x 10 ‑ 3 x 144 A
  • THD‑I <5 % in rated operation
  • Rated load power 7.5 ‑ 117 HP
  • Insulation class H
  • Ambient temperature 14 °F to +113 °F
  • Degree of protection IP 00
Advantages
  • Sinusoidal current consumption from the main in devices with uncontrolled B6U diode rectifiers
  • Support compliance with EN 61000‑3‑2, EN 61000‑3‑12
  • Support compliance with IEEE 519, D‑A‑CH‑CZ
  • Power factor >0.95 at rated current
  • Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor
  • Harmonic filter with minimum capacitive reactive power
  • Very good corrosion protection and low noise thanks to vacuum impregnation
  • Operation at 50 ‑ 60 Hz possible
  • Use of the HF1K as a central hum filter for multiple converters possible
ß W J

  back to choices show all versions
 
 
  PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet
 
 
HF1K 7-480-0
HF1K 13-480-0
HF1K 18-480-0
HF1K 24-480-0
HF1K 30-480-0
HF1K 50-480-0
HF1K 70-480-0
HF1K 100-480-0
Operating data
Rated voltage
3 x 480 Vac
3 x 480 Vac
3 x 480 Vac
3 x 480 Vac
3 x 480 Vac
3 x 480 Vac
3 x 480 Vac
3 x 480 Vac
Rated current
3 x 10 A
3 x 19 A
3 x 26 A
3 x 35 A
3 x 43 A
3 x 73 A
3 x 102 A
3 x 144 A
THD‑I
5 % (nominal load)
5 % (nominal load)
5 % (nominal load)
5 % (nominal load)
5 % (nominal load)
5 % (nominal load)
5 % (nominal load)
5 % (nominal load)
Rated load power
7.5 HP
14.3 HP
19.5 HP
26 HP
33.8 HP
58.5 HP
81.9 HP
117 HP
Description of the load
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Overrating Capacity
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
Efficiency
99 %
99 %
99 %
99 %
99 %
99 %
99 %
99 %
Power loss
90 W
160 W
180 W
230 W
290 W
412 W
550 W
750 W
Capacitive idle power
20 kVAr
22 kVAr
35 kVAr
46 kVAr
71 kVAr
12 kVAr
162 kVAr
228 kVAr
Input
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
Approvals
Approvals
cURus
cURus
cURus
cURus
cURus
cURus
cURus
cURus
Environment
Ambient temperature
14 °F to +113 °F,
without condensation
14 °F to +113 °F,
without condensation
14 °F to +113 °F,
without condensation
14 °F to +113 °F,
without condensation
14 °F to +113 °F,
without condensation
14 °F to +113 °F,
without condensation
14 °F to +113 °F,
without condensation
14 °F to +113 °F,
without condensation
Type of cooling
Air natural
Air natural
Air natural
Air natural
Air natural
Air natural
Air natural
Air natural
MTBF @ 122 °F/500 V (Mil‑HB‑217F)
>500.000 h
@ 104 °F / 480 Vac
>500.000 h
@ 104 °F / 480 Vac
>500.000 h
@ 104 °F / 480 Vac
>500.000 h
@ 104 °F / 480 Vac
>500.000 h
@ 104 °F / 480 Vac
>500.000 h
@ 104 °F / 480 Vac
>500.000 h
@ 104 °F / 480 Vac
>500.000 h
@ 104 °F / 480 Vac
Safety and protection
Type
Open type
Open type
Open type
Open type
Open type
Open type
Open type
Open type
Insulation class
H
H
H
H
H
H
H
H
IP 00
IP 00
IP 00
IP 00
IP 00
IP 00
IP 00
IP 00
Safety class
I
I
I
I
I
I
I
I
Terminal and mounting
Terminals phase
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Copper tab, M10 bolt
Copper tab, M12 bolt
Copper tab, M12 bolt
Connection type
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M8
Bolt, M8
Fixing method
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Measures and weights
Weight
30.86 lbs
61.73 lbs
68.34 lbs
79.81 lbs
130.29 lbs
166.45 lbs
275.58 lbs
359.35 lbs
  Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture
Notes
*
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
Order numbers
Order Number
HF1K 7‑480‑0
HF1K 13‑480‑0
HF1K 18‑480‑0
HF1K 24‑480‑0
HF1K 30‑480‑0
HF1K 50‑480‑0
HF1K 70‑480‑0
HF1K 100‑480‑0