Primary switched mode power supply, PC 1AC

Primary switched mode power supply, PC 1AC, PC 1AC
Data Standards/Certifications Applications Downloads
General Data
  • Nominal input voltage: AC 100 ‑ 240 V
  • Nominal output voltage: DC 12 ‑ 48 V
  • Nominal output current: 5 ‑ 20 A
  • Ambient temperature ‑13 °F / ‑25 °C to +158 °F / +70 °C
  • Efficiency up to 93 %
  • Protection index IP 20
Advantages
  • Stabilized and adjustable output voltage
  • Fast tripping of conventional circuit breakers
  • DC OK indicator
  • Parallel operation
  • Push‑in terminals
  • Robust DIN rail mounting
  • Resistant to transient overvoltages up to 4 kV
W o J #

  back to choices show all versions
 
 
  PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet
                   
 
PC-0112-150-0
PC-0124-050-0
PC-0124-050-4
PC-0124-100-0
PC-0124-100-4
PC-0124-200-0
PC-0124-200-4
PC-0148-050-0
PC-0148-100-0
Special features
Characteristics
Suitable for the medical field
Suitable for the medical field
Suitable for the medical field
Input
Input rated voltage
100 - 240 Vac
100 - 240 Vac
100 - 240 Vac
100 - 240 Vac
100 - 240 Vac
100 - 240 Vac
100 - 240 Vac
100 - 240 Vac
100 - 240 Vac
85 - 264 Vac
(120 - 372 Vdc)
85 - 264 Vac
(120 - 372 Vdc)
85 - 264 Vac
(120 - 372 Vdc)
85 - 264 Vac
(120 - 372 Vdc)
85 - 264 Vac
(120 - 372 Vdc)
85 - 264 Vac
(120 - 372 Vdc)
85 - 264 Vac
(120 - 372 Vdc)
85 - 264 Vac
(120 - 372 Vdc)
85 - 264 Vac
(120 - 372 Vdc)
Input voltage derating
‑2.5 %/Vac < 100 Vac
‑2.5 %/Vac < 97 Vac
‑2,5 %/Vac < 97 Vac
‑2.5 %/Vac < 100 Vac
‑2,5 %/Vac < 100 Vac
‑2.5 %/Vac < 100 Vac
‑2,5 %/Vac < 100 Vac
‑2.5 %/Vac < 100 Vac
‑2.5 %/Vac < 100 Vac
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
Input rated current (rated load)
2.07 A (100 Vac) / 0,95 A (230 Vac)
2.25 A (100 Vac) / 1.2 A (230 Vac)
2,3 A (100 Vac) / 1,24 A (230 Vac)
2.74 A (100 Vac) / 1.25 A (230 Vac)
2,74 A (100 Vac) / 1,25 A (230 Vac)
5.56 A (100 Vac) / 2.23 A (230 Vac)
5,56 A (100 Vac) / 2,23 A (230 Vac)
2.68 A (100 Vac) / 1.19 A (230 Vac)
5.15 A (100 Vac) / 2.22 A (230 Vac)
Starting current limiter
< 30 A, NTC (active)
< 30 A, NTC
< 30 A, NTC (active)
< 30 A, NTC (active)
< 30 A, NTC
< 30 A, NTC (active)
< 30 A, NTC (active)
< 30 A, NTC (active)
< 30 A, NTC (active)
Switch‑on time
0.71 s (100 Vac) / 0.43 s (230 Vac)
0.25 s (100 Vac) / 0.2 s (230 Vac)
0,25 s (100 Vac) / 0,2 s (230 Vac)
1.3 s (100 Vac) / 0.25 s (230 Vac)
1,3 s (100 Vac) / 0,25 s (230 Vac)
0.45 s (100 Vac) / 0.2 s (230 Vac)
0,45 s (100 Vac) / 0,2 s (230 Vac)
0.68 s (100 Vac) / 0.31 s (230 Vac)
0.45 s (100 Vac) / 0.2 s (230 Vac)
Mains buffering (rated load)
28 ms (100 Vac) / 28 ms (230 Vac)
10 ms (100 Vac) / 80 ms (230 Vac)
10 ms (100 Vac) / 80 ms (230 Vac)
15 ms (100 Vac) / 17 ms (230 Vac)
15 ms (100 Vac) / 17 ms (230 Vac)
20 ms (100 Vac) / 20 ms (230 Vac)
8 ms (100 Vac) / 20 ms (230 Vac)
21 ms (100 Vac) / 21 ms (230 Vac)
20 ms (100 Vac) / 20 ms (230 Vac)
Power factor
0.91 (active PFC)
0.5
0,47
0.92 (active PFC)
0,92
0.98 (active PFC)
0,98
0.92 (active PFC)
0.92 (active PFC)
Input fuse internal
6.3 A
4 A
4AT
6.3 A
6,3 AT
10 A
10 AT
6.3 A
10 A
Recommended back‑up fuse (circuit breaker)
10 A, 16 A,
characteristic B, C
6 A, 10 A, 16 A,
characteristic B, C
6A, 10 A, 16 A,
characteristic B, C
10 A, 16 A,
characteristic B, C
10 A, 16 A,
characteristic B, C
10 A, 16 A,
characteristic B, C
10 A, 16 A,
characteristic B, C
10 A, 16 A,
characteristic B, C
10 A, 16 A,
characteristic B, C
Transient surge voltage protection
Varistor
Varistor
Varistor
Varistor
Varistor
Varistor
Varistor
Varistor
Varistor
Output
Output rated voltage
12 Vdc
24 Vdc
24 Vdc
24 Vdc
24 Vdc
24 Vdc
24 Vdc
48 Vdc
48 Vdc
11.5 – 15 Vdc
23 – 28.5 Vdc
11,8 – 27,5 Vdc
23 – 28.5 Vdc
23 – 28,5 Vdc
23 – 28,5 Vdc
23 – 28,5 Vdc
40 – 56 Vdc
40 – 56 Vdc
Output rated current
15 A
5 A
5 A
10 A
10 A
20 A
20 A
5 A
10 A
Output limited current
typ. 16.5 A (constant current)
typ. 5.5 A (constant current)
typ. 16.5 A (constant current)
typ. 11 A (constant current)
typ. 11 ‑ 13 A(constant current)
typ. 22 A (constant current)
typ. 22 A(constant current)
typ. 5.5 A (constant current)
typ. 11 A (constant current)
Tripping of LS circuit breakers
max. B4
max. B4
max. B4
max. B6, C2
max. B4
max. B6, C6, K4
max. B4
max. B6, C4, K2
max. B6, C4, K2
Parallel connection
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Serial operation
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Power dissipation, no load/rated load
4.4 W / 21.8 W (230 Vac)
1.2 / 14.6 W (230 Vac)
1,2 W / 14,6 W (230 Vac)
6.6 / 24.4 W (230 Vac)
6,6 W / 24,4 W (230 Vac)
7.2 / 42.4 W (230 Vac)
7,2 W / 42,4 W (230 Vac)
7 W / 40,8 W (230 Vac)
11.7 / 36.3 W (230 Vac)
Max. power losses
24.7 W (100 Vac / 12 V / 15 A)
19.4 W (100 Vac / 24 V / 5 A)
19,4 W (100 Vac / 24 V / 5 A)
31.3 W (100 Vac / 24 V / 10 A)
31,3 W (100 Vac / 24 V / 10 A)
68.3 W (100 Vac / 24 V / 20 A)
68,3 W (100 Vac / 24 V / 10 A)
26,5 W (100 Vac / 48 V / 5 A)
64.9 W (100 Vac / 48 V / 10 A)
Efficiency
typ. 90 %
typ. 89 %
typ. 89 %
typ. 91 %
typ. 91 %
typ. 92 %
typ. 92 %
typ. 92 %
typ. 93 %
Ripple factor
typ. 35 mVss
typ. 30 mVss
typ. 30 mVss
typ. 50 mVss
typ. 50 mVss
typ. 70 mVss
typ. 70 mVss
typ. 35 mVss
typ. 80 mVss
Resistance to reverse feed max.
35 Vdc
35 Vdc
0 Vdc
35 Vdc
0 Vdc
35 Vdc
0 Vdc
63 Vdc
63 Vdc
Over‑voltage‑protection
max. 20 Vdc
max. 41 Vdc
max. 41 Vdc
max. 40 Vdc
max. 40 Vdc
max. 40 Vdc
max. 40 Vdc
max. 60 Vdc
max. 60 Vdc
Signaling
Typ. switching threshold for LED and signal output (DC OK)
LED: Uout > 11,2 V, 
signal output: Uout > 16 V (typ.)
Uout > 21,5 V
Uout > 21,5 V
Status indicator
LED green
LED green
LED green
LED green
LED green
LED green
LED green
LED green
LED green
Signal output
Relay contact
Relay contact
Relay contact, max. 30 V / 1 A
Relay contact
Relay contact, max. 30 V / 1 A
Relay contact
Relay contact, max. 30 V / 1 A
Relay contact
Relay contact
Approvals
Approvals
cURus, cULus, GL
cURus, cULus, GL
cURus, cULus (UL 60601), GL
cURus, cULus, GL
cURus, cULus (UL 60601), GL
cURus, cULus, GL
cURus, cULus (UL 60601), GL
cURus, cULus, GL
cURus, cULus, GL
Environment
Type of cooling
natural convection
natural convection
natural convection
natural convection
natural convection
natural convection
natural convection
natural convection
natural convection
Ambient temperature
-13 °F to +158 °F
-13 °F to +158 °F
-13 °F to +158 °F
-13 °F to +158 °F
-13 °F to +158 °F
-13 °F to +158 °F
-13 °F to +158 °F
-13 °F to +158 °F
-13 °F to +158 °F
Storage temperature
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
Derating
-5 %/K > +140 °F @ 196 - 264 Vac
-2.5 %/K > +122 °F @ 85 - 195 Vac
-5 %/K > +140 °F @ 196 - 264 Vac
-2.5 %/K > +122 °F @ 85 - 195 Vac
-5 %/K > +140 °F @ 196 - 264 Vac
-2.5 %/K > +122 °F @ 85 - 195 Vac
-5 %/K > +140 °F @ 196 - 264 Vac
-2.5 %/K > +122 °F @ 85 - 195 Vac
-5 %/K > +140 °F @ 196 - 264 Vac
-2.5 %/K > +122 °F @ 85 - 195 Vac
-5 %/K > +140 °F @ 196 - 264 Vac
-2.5 %/K > +122 °F @ 85 - 195 Vac
-5 %/K > +140 °F @ 196 - 264 Vac
-2.5 %/K > +122 °F @ 85 - 195 Vac
-5 %/K > +140 °F @ 196 - 264 Vac
-2.5 %/K > +122 °F @ 85 - 195 Vac
-5 %/K > +140 °F @ 196 - 264 Vac
-2.5 %/K > +122 °F @ 85 - 195 Vac
Required minimum spacing (left/right)
0.00 inch
0.00 inch
0.00 inch
0.00 inch
0.00 inch
0.00 inch
0.00 inch
0.00 inch
0.00 inch
Required minimum spacing (over/under)
1.97 inch
1.97 inch
1.97 inch
1.97 inch
1.97 inch
1.97 inch
1.97 inch
1.97 inch
1.97 inch
Mounting position
horizontal for standard rail DIN TS35
horizontal for standard rail DIN TS35
horizontal for standard rail DIN TS35
horizontal for standard rail DIN TS35
horizontal for standard rail DIN TS35
horizontal for standard rail DIN TS35
horizontal for standard rail DIN TS35
horizontal for standard rail DIN TS35
horizontal for standard rail DIN TS35
Safety and protection
MTBF in acc. IEC 61709 (SN 29500)
> 500 000 h
> 500 000 h
> 500 000 h
> 500 000 h
> 500 000 h
> 500 000 h
> 500 000 h
> 500 000 h
> 500 000 h
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
Safety class
I, with PE connection
I, with PE connection
I
I, with PE connection
I
I, with PE connection
I
I, with PE connection
I, with PE connection
Terminal and mounting
Terminals signalling (direct plug‑in technology Push‑in)
max 2,5 mm²
max 2,5 mm²
max 2,5 mm²
max. 2,5 mm²
max 2,5 mm²
max 2,5 mm²
Terminals input (direct plug‑in technology Push‑in)
max 2,5 mm²
max 2,5 mm²
max 2,5 mm²
max. 2,5 mm²
max 2,5 mm²
max 2,5 mm²
Terminals output (direct plug‑in technology Push‑in)
max 2,5 mm²
max 2,5 mm²
max 2,5 mm²
max 2,5 mm²
max 2,5 mm²
max. 6 mm²
max 2,5 mm²
max 2,5 mm²
max 2,5 mm²
Measures and weights
Weight
2.05 lbs
1.30 lbs
1.43 lbs
2.05 lbs
1.43 lbs
3.53 lbs
3.75 lbs
2.05 lbs
3.53 lbs
Dimension (W x H x D)
2.17 x 5 x 6.34 inch
1.65 x 5 x 4.96 inch
1.65 x 5 x 5.53 inch
2.17 x 5 x 6.34 inch
2.17 x 5 x 6.69 inch
3.74 x 5 x 6.26 inch
3.74 x 5 x 6.61 inch
2.17 x 5 x 6.34 inch
3.74 x 5 x 6.26 inch
  Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture
Order numbers
Order Number
PC‑0112‑150‑0
PC‑0124‑050‑0
PC‑0124‑050‑4
PC‑0124‑100‑0
PC‑0124‑100‑4
PC‑0124‑200‑0
PC‑0124‑200‑4
PC‑0148‑050‑0
PC‑0148‑100‑0