Primary switched mode power supply, Economy PVSE 400

Primary switched mode power supply, Economy PVSE 400, PVSE 400
Data Standards/Certifications Applications Downloads
General Data
  • Input rated voltage 3 x 400 ‑ 500 Vac
  • Output rated voltage 24 ‑ 48 Vdc
  • Output rated current 10 ‑ 40 A
  • Ambient temperature ‑13 °F / ‑25 °C to +158 °F / 70 °C
  • Efficiency up to 95 %
  • Protection index IP 20
Advantages
  • Stabilized and adjustable output voltage
  • Up to 200 % Real Power Boost for 4 seconds
  • Top Boost to trip conventional circuit breakers
  • DC OK indicator
  • Parallel connection option
  • Service‑friendly spring‑loaded connector system
  • Can be supplied with isolated DC OK signalling function
  • Panel installation on mounting rails
W o J

  back to choices show all versions
 
 
  PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet
             
 
PVSE 400/24-10
PVSE 400/24-20
PVSE 400/24-40
PVSE 400/30-25
PVSE 400/48-10
PVSE 400/48-20
Input
Input rated voltage
3 x 400 - 500 Vac
3 x 400 - 500 Vac
3 x 400 - 500 Vac
3 x 400 - 500 Vac
3 x 400 - 500 Vac
3 x 400 - 500 Vac
340 - 550 Vac (480 - 780 Vdc)
340 - 550 Vac (480 - 780 Vdc)
340 - 550 Vac (480 - 780 Vdc)
340 - 550 Vac (480 - 780 Vdc)
340 - 550 Vac (480 - 780 Vdc)
340 - 550 Vac (480 - 780 Vdc)
Input rated current (rated load)
0.6 A (3 x 340 Vac)
1.1 A (3 x 340 Vac)
2 A (3 x 340 Vac)
1.6 A (3 x 340 Vac)
1.1 A (3 x 340 Vac)
2 A (3 x 340 Vac)
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
44 Hz - 66 Hz / 0 Hz
Starting current limiter
<30 A, NTC
<30 A, NTC
<30 A, NTC
<30 A, NTC
<30 A, NTC
<30 A, NTC
Input fuse internal
3 x 1.6 A (slow‑blow)
3 x 2.5 A (slow‑blow)
3 x 6.3 A (slow‑blow)
3 x 6.3 A (slow‑blow)
3 x 6.3 A (slow‑blow)
3 x 6.3 A (slow‑blow)
Recommended back‑up fuse (circuit breaker)
6 A, 10 A, 16 A, characteristics B, C
6 A, 10 A, 16 A, characteristics B, C
10 A, 16 A, characteristics B, C
10 A, 16 A, characteristics B, C
10 A, 16 A, characteristics B, C
10 A, 16 A, characteristics B, C
Harmonic correction
passive
passive
passive
passive
passive
passive
Mains buffering (rated load)
22.6 / 51.5 ms
(400 / 500 Vac)
13.2 / 36.8 ms
(400 / 500 Vac)
15.6 / 42.9 ms
(400 / 500 Vac)
15.6 / 42.9 ms
(400 / 500 Vac)
12 / 35 ms
(400 / 500 Vac)
15.6 / 42.9 ms
(400 / 500 Vac)
Transient surge voltage protection
Varistor
Varistor
Varistor
Varistor
Varistor
Varistor
Output
Output rated voltage
24 Vdc
24 Vdc
24 Vdc
30 Vdc
48 Vdc
48 Vdc
22.8 ‑ 28.8 Vdc
22.8 ‑ 28.8 Vdc
22.8 ‑ 28.8 Vdc
27 ‑ 43 Vdc
37 ‑ 51 Vdc
37 ‑ 51 Vdc
Resistance to reverse feed max.
35 Vdc
35 Vdc
35 Vdc
63 Vdc
63 Vdc
63 Vdc
Output rated current
10 A
20 A
40 A
25 A
10 A
20 A
Parallel connection
Yes
Yes
Yes
Yes
Yes
Yes
Power Boost
20 A / 4 s (15 A / 8 s)
40 A / 4 s (30 A / 8 s)
60 A / 4 s (50 A / 8 s)
45 A / 4 s (35 A / 8 s)
15 A / 4 s (12.5 A / 8 s)
30 A / 4 s (25 A / 8 s)
Overload behaviour
Constant current
Constant current
Constant current
Constant current
Constant current
Constant current
max. Power loss idling/nominal load
7.8 / 19.9 W
8.3 / 38.4 W
7.0 / 66.2 W
5.2 / 47.3 W
8.2 / 38 W
5.2 / 59.2 W
Serial operation
Yes
Yes
Yes
Yes
Yes
Yes
Efficiency
typ. 91.7 %
typ. 92.9 %
typ. 93.1 %
typ. 94.1 %
typ. 93 %
typ. 94.4 %
Ripple factor
typ. 70 mVss
typ. 70 mVss
typ. 70 mVss
typ. 70 mVss
typ. 70 mVss
typ. 70 mVss
70 A / 50 ms
80 A / 50 ms
100 A / 50 ms
85 A / 50 ms
55 A / 50 ms
80 A / 50 ms
Signaling
Power Good (DC OK)
LED green, LED red
LED green, LED red
LED green, LED red
LED green, LED red
LED green, LED red
LED green, LED red
Potential‑free signal contact
Yes
Yes
Yes
Yes
Yes
Yes
Stand‑by‑input
Yes
Yes
Yes
Yes
Yes
Yes
Approvals
Approvals
cURus, cULus
cURus, cULus
cURus, cULus
cURus, cULus
cURus, cULus
cURus, cULus
Environment
Ambient temperature
‑13 °F to 158° F
‑13 °F to 158° F
‑13 °C to 131 °F
‑13 °F to 158° F
‑13 °F to 158° F
‑13 °F to 158° F
Storage temperature
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
-13 °F to +185 °F
Derating
‑3 %/K > +122 °F
‑3 %/K > +122 °F
‑5 %/K > +113 °F
‑3 %/K > 122 °F
‑3 %/K > +122 °F
‑3 %/K > +122 °F
Safety and protection
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
Safety class
I, with PE connection
I, with PE connection
I, with PE connection
I, with PE connection
I, with PE connection
I, with PE connection
Terminal and mounting
Terminals input, (spring clamp terminal, pluggable)
max. 2.5 mm²
max. 2.5 mm²
max. 2.5 mm²
max. 2.5 mm²
max. 2.5 mm²
max. 2.5 mm²
Terminals output, (spring clamp terminal, pluggable)
max. 2.5 mm²
max. 10 mm²
max. 10 mm²
max. 10 mm²
max. 10 mm²
max. 10 mm²
Terminals signalling, (spring clamp terminal, pluggable)
max. 0.5 mm²
max. 0.5 mm²
max. 0.5 mm²
max. 0.5 mm²
max. 0.5 mm²
max. 0.5 mm²
Mounting position
vertical
vertical
vertical
vertical
vertical
vertical
Fixing method
DIN Rail system TS35
DIN Rail system TS35
DIN Rail system TS35
DIN Rail system TS35
DIN Rail system TS35
DIN Rail system TS35
Measures and weights
Weight
2.87 lbs
3.88 lbs
6.68 lbs
6.68 lbs
3.88 lbs
6.68 lbs
  Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture
Accessory
Connector for signalling
PV-CON (optional)
PV-CON (optional)
PV-CON (optional)
PV-CON (optional)
PV-CON (optional)
PV-CON (optional)
Side DIN rail mounting
PV-TS35M (optional)
PV-TS35M (optional)
PV-TS35M (optional)
PV-TS35M (optional)
PV-TS35M (optional)
PV-TS35M (optional)
Direct screw fastening plate for lateral mounting    
PV‑WB2 (optional)
PV‑WB2 (optional)
PV‑WB2 (optional)
PV‑WB2 (optional)
PV‑WB2 (optional)
PV‑WB2 (optional)
Order numbers
Order Number
PVSE 400/24‑10
PVSE 400/24‑20
PVSE 400/24‑40
PVSE 400/30‑25
PVSE 400/48‑10
PVSE 400/48‑20