Harmonic filter HF1K 400

Harmonic filter HF1K 400, HF1K 400
Data Standards/Certifications Applications Downloads
General Data
  • Rated voltage 3 x 400 Vac
  • Rated current 3 x 10 ‑ 3 x 144 A
  • THD‑I <8 % in rated operation
  • Load rated capacity 5.5 ‑ 90 kW
  • Insulation class H
  • Ambient temperature ‑10 °C to +45 °C
  • Degree of protection IP 00
Advantages
  • Sinusoidal current consumption from the main in devices with uncontrolled B6U diode rectifiers
  • Compliance with EN 61000‑3‑2, EN 61000‑3‑12
  • Support in the compliance with IEEE 519, D‑A‑CH‑CZ
  • Cos(phi)>0,95 at rated current
  • Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor
  • Harmonic filter with minimum capacitive idle reactive power
  • Very good corrosion protection and low noise thanks to BLOCKIMPEX vacuum impregnation
  • Operation at 50 ‑ 60 Hz possible
  • Use of the HF1K as a central sum filter for multiple converters possible
ß W J

  back to choices show all versions
 
 
  PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet
 
 
HF1K 7-400
HF1K 13-400
HF1K 18-400
HF1K 24-400
HF1K 30-400
HF1K 50-400
HF1K 70-400
HF1K 100-400
Operating data
Rated voltage
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
Rated current
3 x 10 A
3 x 19 A
3 x 26 A
3 x 35 A
3 x 43 A
3 x 72 A
3 x 101 A
3 x 144 A
THD‑I
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
Rated load power*
5.5 kW
11 kW
15 kW
20 kW
26 kW
45 kW
63 kW
90 kW
Description of the load
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Overrating Capacity
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
Efficiency
99.0 %
99.0 %
99.0 %
99.0 %
99.0 %
99.0 %
99.0 %
99.0 %
Power loss
90.0 W
160.0 W
180.0 W
230.0 W
290.0 W
412.0 W
550.0 W
750.0 W
Capacitive idle power
1.7 kVAr
1.8 kVAr
2.9 kVAr
3.8 kVAr
4.9 kVAr
10.0 kVAr
13.5 kVAr
19.0 kVAr
Input
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
Approvals
Approvals
cURus
cURus
cURus
cURus
cURus
cURus
cURus
cURus
Environment
Ambient temperature
-10 °C to +45 °C,
without condensation
-10 °C to +45 °C,
without condensation
-10 °C to +45 °C,
without condensation
-10 °C to +45 °C,
without condensation
-10 °C to +45 °C,
without condensation
-10 °C to +45 °C,
without condensation
-10 °C to +45 °C,
without condensation
-10 °C to +45 °C,
without condensation
Type of cooling
AN
AN
AN
AN
AN
AN
AN
AN
MTBF @ 50°C/500 V (Mil‑HB‑217F)
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
Safety and protection
Type
Open type
Open type
Open type
Open type
Open type
Open type
Open type
Open type
Insulation class
H
H
H
H
H
H
H
H
IP 00
IP 00
IP 00
IP 00
IP 00
IP 00
IP 00
IP 00
Safety class
I
I
I
I
I
I
I
I
Terminal and mounting
Terminals phase
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Copper tab, M10 bolt
Copper tab, M12 bolt
Copper tab, M12 bolt
Terminals PE
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M8
Bolt, M8
Fixing method
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Measures and weights
Weight
14 kg
28 kg
31 kg
36,2 kg
59,1 kg
75,5 kg
125 kg
163 kg
  Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture
Notes
*
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
Order numbers
Order Number
HF1K 7‑400
HF1K 13‑400
HF1K 18‑400
HF1K 24‑400
HF1K 30‑400
HF1K 50‑400
HF1K 70‑400
HF1K 100‑400