Harmonic Filter HF1K

Harmonic Filter HF1K, HF1K
Data Standards/Certifications Applications Downloads
General Data
  • Rated voltage 3 x 400 Vac
  • Rated current 3 x 10.00 ‑ 3 x 144.00 A
  • THD‑I 8 % in rated operation
  • Load rated capacity 5.5 ‑ 90 kW
  • Insulation class H
  • Ambient temperature ‑10° C to +40° C
  • Degree of protection IP 00
Advantages
  • Sinusoidal current consumption from the mains in devices with uncontrolled B6U diode rectifiers
  • Compliance with EN 61000‑3‑2, EN 61000‑3‑12
  • Support in the compliance with IEEE 519, D‑A‑CH‑CZ
  • cos(phi)>0,95 at rated current
  • Hardly any intermediate circuit voltage dip by comparison with a 4 % uK line reactor
  • Harmonic filter with minimum capacitive idle reactive power
  • Very good corrosion protection and low noise thanks to BLOCKIMPEX vacuum impregnation
  • Operation at 50 ‑ 60 Hz possible
  • Use of the HF1K as a central hum filter for multiple converters possible
ß W

  back to choices show all versions
 
 
  PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet PDF Data sheet
 
HF1K 7-400
HF1K 13-400
HF1K 18-400
HF1K 24-400
HF1K 30-400
HF1K 50-400
HF1K 70-400
HF1K 100-400
Operating data
Rated voltage
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
3 x 400 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
360‑440 Vac
Rated current
3 x 10 A
3 x 19 A
3 x 26 A
3 x 35 A
3 x 43 A
3 x 72 A
3 x 101 A
3 x 144 A
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
THD‑I
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
8 % (nominal load)
Rated load power*
5.5 kW
11 kW
15 kW
20 kW
26 kW
45 kW
63 kW
90 kW
Description of the load
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Symmetrical loading by converters with B6U input rectifiers
Overrating Capacity
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
150 % for 60 sec. every 10 min.
Power loss
90.0 W
160.0 W
180.0 W
230.0 W
290.0 W
412.0 W
550.0 W
750.0 W
Efficiency
99 %
99 %
99 %
99 %
99 %
99 %
99 %
99 %
Capacitive idle reactive power
1.7 kVAr
1.8 kVAr
2.9 kVAr
3.8 kVAr
4.9 kVAr
10.0 kVAr
13.5 kVAr
19.0 kVAr
Approvals
Approvals
cURus
cURus
cURus
cURus
cURus
cURus
cURus
cURus
Environment
Ambient temperature
-10° C to +40° C,
without condensation
-10° C to +40° C,
without condensation
-10° C to +40° C,
without condensation
-10° C to +40° C,
without condensation
-10° C to +40° C,
without condensation
-10° C to +40° C,
without condensation
-10° C to +40° C,
without condensation
-10° C to +40° C,
without condensation
Cooling method
AN
AN
AN
AN
AN
AN
AN
AN
MTBF @ 50°C/500 V (Mil‑HB‑217F)
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
>500.000 h
@ 40°C/400Vac
Safety and protection
Type
open type
open type
open type
open type
open type
open type
open type
open type
Class of Insulation System
H
H
H
H
H
H
H
H
IP 00
IP 00
IP 00
IP 00
IP 00
IP 00
IP 00
IP 00
Safety class
I
I
I
I
I
I
I
I
Terminal and mounting
Connections phase
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Screw clamp, 10 mm²
Copper tab, M8 bolt
Copper tab, M8 bolt
Copper tab, M8 bolt
Connections PE
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M6
Bolt, M8
Bolt, M8
Bolt, M8
Fixing method
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Mounting lugs
Measures and weights
Weight
14.00 kg
28.00 kg
31.00 kg
36.20 kg
59.10 kg
75.50 kg
125.00 kg
163.00 kg
  Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture Dimension Picture
Notes
*
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
IE2 efficiencies of the motors and an efficiency
>96 % assumed
Order numbers
Order Number
HF1K 7‑400
HF1K 13‑400
HF1K 18‑400
HF1K 24‑400
HF1K 30‑400
HF1K 50‑400
HF1K 70‑400
HF1K 100‑400